Operation With Continuous Send; Transmission Of A Block Of One To 512 Bytes; Transmission Of A Block Of More Than 512 Bytes; Table 40: Transmission Of A Block Of One To 512 Bytes - WAGO 750-652 Manual

I/o-system 750
Hide thumbs Also See for 750-652:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-652 Serial Interface RS-232 / RS-485
8.3.5

Operation with Continuous Send

8.3.5.1

Transmission of a Block of One to 512 Bytes

The output buffer is filled up with data up to number n (n ≤ 512 bytes)
To transmit the buffer content, the bit 3 (SC) of the control byte 0 is set by the
controller. The I/O module begins with the data transmission and the bit 3
(BUF_E) of the status byte 1 is reset.
If all data is transmitted, the bit 3 (BUF_E) of the status byte 1 is set.
The controller takes bit 3 (SC) of the control byte 0 back from the controller. The
end of the transmission from the I/O module is detected this way.

Table 40: Transmission of a Block of One to 512 Bytes

Control byte 0
'0110.1001'
Status byte 0
'0XXX.X0X1'
Control byte 0
'0110.1000'
Status byte 0
'0XXX.X0X0'
Status byte 0
'0XXX.X0X1'
Control byte 0
'0XXX.0XX0'
8.3.5.2

Transmission of a Block of More than 512 Bytes

The output buffer is filled up with data up to number 512 bytes.
To transmit the buffer content, the bit 3 (SC) of the control byte 0 is set by the
controller. The I/O module begins with the data transmission and the bit 3
(BUF_E) of the status byte 1 is reset.
During transmission, the output buffer continues to be filled up by the controller.
Bit 3 (SC) of control byte 0 is set by the controller as long as data should be
transmitted. The I/O module acknowledges data transmission by resetting bit 3
(BUF_E) in status byte 1.
Then bit 3 (SC) of control byte 0 is taken back by the controller. The end of the
transmission from the I/O module is detected this way.
Manual
Version 1.4.0
Control byte 1
'0XXX. X101'
Controller fills the output buffer with 46 bytes and set bit
3 (SC) of the control byte 0 for the start of the
transmission.
Status byte 1
'0000. 1XXX'
I/O module confirms the acceptance of the data.
Control byte 1
'0XXX. X101'
Controller takes bit 0 (TR) of the control byte 0 back.
Status byte 1
'0XXX. 0XXX'
I/O module begins with the data transmission via the
serial interface.
Status byte 1
'0000. 1XXX'
All data is transmitted via the serial interface.
Control byte 1
'0XXX. 1XXX'
Controller takes bit 3 (TR) of the control byte 0 back.
Commissioning
55