Service values
51
51
Output test
0
Control mode according to the operating state
1
All outputs OFF
2
Burner stage 1 ON
3
Burner stages 1 and 2 ON
4
D.h.w. charging pump ON
D.h.w. diverting valve OPEN
5
Heating circuit pump 1
Boiler pump ON
6
Mixing valve 1 open
7
Mixing valve 2 close
8
Multi-functional output ON
9
Mult-functional output ON
52
52
Input test
0
Boiler sensor
1
D.h.w. sensor 1
2
D.h.w. sensor 2
Buffer storage tank sensor 2
H2
4
Outside sensor
5
Room sensor
6
Return sensor
7
Flue gas sensor
Collector sensor
8
Buffer storage tank sensor 1
9
Display of input H1
10
Display switching status input E1.
53
53
Display of plant type
Actual values
55
55
Actual value of flow temperature (TVx)
Input B1
56
56
Actual value of boiler temperature (TKx)
Input B2/B4
57
-
Actual value of common flow temperature
58
58
Actual value of cascade return temperature
59
59
Actual value 1 of buffer storage tank temperature
60
-
Actual value 2 of buffer storage tank temperature
61
61
Actual value 1 of d.h.w. temperature (TBWx)
(Higher temperature)
62
62
Actual value 2 of d.h.w. temperature (TBWx)
(Lower temperature)
63
63
Display of max. flue gas temperature (TGxmax)
To make a reset to the current value, press the + and –
buttons simultaneously for 3 seconds
64
-
Actual value of collector temperature (B6)
65
65
Attenuated outside temperature
66
66
Composite outside temperature
67
-
Outside temperature source
- - . - -
00.01...14.16
Siemens Building Technologies
Landis & Staefa Division
1.1.1 Overview of heating engineer parameters
K4
K4 / K5
Q3/Y3
Q3 / Y3
Q2
Q2
Y1
Y2
K6
K7
B2
B3
B31/H2
B31/H2
B31/H2
B9
A6
B7
B8/B6
B8/B6
B4
H1
E1
(TAxged)
(Taxgem)
No signal
Address
Basic Documentation RVA63.242, RVA53.242
Handling
0...9
0...10
Flow temperature sensor HK1
1...150
0...140
0...140
0...140
0 ...140
0 ...140
0...140
0...140
0...140
0...350
0...350
(Pt1000)
0...230
(Ni1000)
-50...+50
-50...+50
- -:- / 00.01...14.16
-
1
0
-
1
0
-
1
-
°C
1
-
°C
1
-
°C
1
-
°C
1
-
°C
1
-
°C
1
-
°C
1
-
°C
1
-
°C
1
-
°C
1
-
°C
0.5
-
°C
0.5
-
-
1
-
27/218
CE1P2373E
26.03.2001