5.10 Control of boiler pump

Boiler pump control mode can be selected.
The setting defines the criteria according to which the boiler pump shall be operated.
Setting range
0 / 1
The settings have the following meaning:
0
The boiler pump operates when there is a demand for heat.
In that case, the boiler pump responds to locking signals.
1
The boiler pump operates when there is a demand for heat or when the burner
operates. In that case, the boiler pump does not respond to locking signals
(protective boiler start-up).
Basic Documentation RVA63.242, RVA53.242
Description of OEM settings
Unit
Factory setting
0
159/218
CE1P2373E
26.03.2001