D.h.w. values
3.16 Nominal setpoint of d.h.w. temperature
(TBWw)
D.h.w. heating only if there is demand for it.
Possibility of using 2 different d.h.w. temperature setpoints.
Setting range
TBWR...TBWmax
TBWR Reduced setpoint of d.h.w. temperature (setting on line 120)
TBWmax Maximum nominal setpoint of d.h.w. temperature (setting on line 50
The temperature setpoint during normal d.h.w. operation will be changed.
0
10
20
30
26
Setting "Nominal setpoint of d.h.w. temperature"
120
Setting "Reduced setpoint of d.h.w. temperature"
50
Setting "Maximum nominal setpoint of d.h.w. temperature"
OEM
D.h.w. heating has 2 different setpoints that can be used:
Nominal setpoint of the d.h.w. temperature: It ensures d.h.w. temperature required
during main occupancy times.
Reduced setpoint of d.h.w. temperature (setting on line 120): It ensures the d.h.w.
temperature required outside main occupancy times.
The times at which these d.h.w. setpoints shall apply can be set with the d.h.w.
program on line 121.
Basic Documentation RVA63.242, RVA53.242
Description of end-user settings
Unit
°C
40
50
60
70
Factory setting
55
)
OEM
80
90
100
°C
55/218
CE1P2373E
26.03.2001