Attenuated Outside Temperature - Siemens RVA63.242 User Manual

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Reset
Process
Effect
Example
Siemens Building Technologies
Landis & Staefa Division

6.7 Attenuated outside temperature

Making use of the building's thermal storage capacity
The attenuated outside temperature is the simulated room temperature of a fictive
building that has no internal heat source. This means that it is only the outside
temperature that affects the room temperature.
No direct setting can be made. The generation of the attenuated outside temperature
cannot be influenced.
It is possible, however, to reset the attenuated outside temperature:
1.
Press the line selection buttons to select line 34.
2.
Press the + / - buttons for 3 seconds.
As soon as the display stops flashing, the attenuated outside temperature is reset
to the actual outside temperature.
The attenuated outside temperature is generated by the controller. It is calculated at
10-minute intervals, based on the actual outside temperature. The factory setting uses
a basic value of 0 °C.
The attenuated outside temperature affects directly only summer / winter changeover.
The attenuated outside temperature acts indirectly, via the composite outside
temperature, on flow temperature control.
TA
°C
17
16
15
14
13
18:00
06:00
TAakt
Actual outside temperature
TAged
Attenuated outside temperature
Basic Documentation RVA53.242, RVA53.242
General control processes
.
TAakt
TAged
18:00
06:00
h
18:00
193/218
CE1P2373E
26.03.2001