4.68 Central stand-by switch

Central operation in the selected range of action.
From the master controller, the heating system can be switched to stand-by in the
selected range of action.
Setting range
0 / 1
This setting can only be made on the master controller (device with setting on
line 140 = 1) and the setting line will only be displayed on this controller!
Entry:
0
Central stand-by circuit is switched off
1
Central stand-by circuit is activated
Segment address
0
1...14
If central stand-by on the master controller is switched on, it can only be switched off
again from that controller!
The central stand-by circuit does not affect d.h.w. heating. This means that the d.h.w. is
heated according to the settings made.
If the central stand-by circuit is activated, the stand-by button
selected range of action flashes.
Basic Documentation RVA63.242, RVA53.242
Description of heating engineer settings
Unit
Increment
Effect
According to the setting made on
line 145
Throughout the segment
Factory setting
0
on all controllers in the
CE1P2373E
26.03.2001