5.20.3 Temperature-time integral

This temperature-time integral generates the locking signal for restricting the heating
circuits.
When generating the locking signal, different procedures are used:
Diagram
Procedure
a to b
Within a foreseeable period of time, the actual boiler return temperature
(TKRx) will lie below TKRmin.
è
Locking signal will be built up
b to c,
Within a foreseeable period of time, the actual boiler return temperature
d to e
(TKRx) will lie within the switching differential (SD).
è
Locking signal will remain at a constant level
c to d,
Within a foreseeable period of time, the actual boiler return temperature
e to f
(TKRx) will lie above the level of TKRmin+SD.
è
Locking signal will be decreased
TKR
TKRx
SD
TKRmin
y
x%
0%
a
TKR
Return temperature
TKRx
Actual boiler return temperature
TKRmin
Minimum limitation of boiler return temperature
SD
Switching differential fixed = 2 K
t
Time
Y
Locking signal
Basic Documentation RVA63.242, RVA53.242