Release Integral Of Burner Stage 2; Temperature-Time Integral - Siemens RVA63.242 User Manual

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Burner stage 2
Note
Switching point
Example
152/218
Siemens Building Technologies
Landis & Staefa Division

5.5 Release integral of burner stage 2

Optimum switching on of burner stage 2.
Adjustment of heat deficit for releasing burner stage 2.
Setting range
0...500
The setting will change the switch-on point for burner stage 2.
Entry:
Increase:
Burner stage 2 will be released when the heat deficit is greater
Decrease:
Burner stage 2 will be released when the heat deficit is smaller
If, with burner stage 1, the boiler temperature falls below the switch-on setpoint (TKw -
SDK/2) by the amount of the release integral set here, the controller will release the
second burner stage.
During the time burner stage 2 is released, the controller will activate and deactivate
burner stage 2 according to the switching differential.

5.5.1 Temperature-time integral

The temperature-time integral is a continuous summation of the temperature differential
over time. In this case, the decisive criterion is the difference by which the boiler
temperature falls below the burner's switch-on setpoint (TKw-SDK/2-TKx).
Through the generation of the temperature-time integral it is not only the period of time
that is considered, but also the extent of the undershoot. This means that when the
crossing is significant, burner stage 2 will be released earlier.
When the release integral (area "a" in the diagram below) has reached the value set
(point in time tF), burner stage 2 will be released.
°C
TKx
52
50
a
48
46
44
a
Release limit
TKw
Boiler temperature setpoint
TKx
Actual value of the boiler temperature
SDK
Switching differential of the boiler
t
Time
tF
Time to release
Basic Documentation RVA63.242, RVA53.242
Description of OEM settings
Unit
°C (K) min
tF
Factory setting
50
TKw+SDK/2
TKw
TKw-SDK/2
t
CE1P2373E
26.03.2001

Hide quick links: