30/106
Siemens
Building Technologies
8
Function block: Plant configuration
This function block only provides selection of the plant type:
8.1
Operating line
Line
Function, parameter
51
Plant type
8.2
General
When commissioning a plant, the respective plant type must be entered first. This
ensures that the functions required for the specific type of plant, the parameters
and operating lines for the settings and displays are activated.
All plant-specific variables and operating lines for use with the other plant types will
be hidden. They will not appear on the display.
Example of entry:
Basic Documentation RVP360
8 Function block: Plant configuration
Factory setting (range)
RVP360
5–1 (4–0, 4-1, 5-0, 5-1, 6-0, 6-1)
5
= heating circuit type 5
1
= d.h.w. type 1
CE1P2546en
2017-07-24