OPERATION
Table 4. Configuration Settings
Description
Available Settings
Change language
[English] [French] [German] [Spanish] [Japanese] [Simplified
Chinese] [Russian] [Korean] [Traditional Chinese]
User password
[Enabled] [Disabled]
If Enabled, the default password is USER.
NOTE If you enter an incorrect password, press any button to
return to the password screen and retry the password.
Audible alarms
[Enabled] [Disabled]
NOTE Disabling audible alarms takes effect instantly and remains
disabled, even after a power cycle. This differs from the mute
feature, by which the audible alarm is temporarily silenced when
any button is pressed but turns on again if a new alarm is
triggered.
Set date and time
Set Month, Day, Year, Hours, Minutes, and Seconds
Date: mm/dd/yyyy
Time: hh:mm:ss
NOTES
1. The date format is dependent on the language selection.
2. Time is a 24-hour clock.
Control commands
[Enabled] [Disabled]
from serial port
If Enabled, control commands are accepted through the serial
port, USB ports, or option card. If Disabled, configuration and load
control commands are restricted to LCD only.
Output voltage
9910-E35: [200V] [208V]
9910-E36: [220V] [230V] [240V]
9910-E66: [200V] [208V] [220V] [230V] [240V] [Auto sensing]
9910-E67: [200V] [208V] [220V] [230V] [240V] [Auto sensing]
NOTE Numerical settings configured in Standby mode take effect
immediately. Auto sensing and settings configured outside of
Standby mode take effect after the next power off and restart.
Selecting auto sensing disables the battery start feature until the
first successful startup on utility power.
For 9910-E66 and 9910-E67 models, the default auto sensing runs at
each startup to set the output voltage.
26
Eaton 9910 UPS and EBM User's Guide

Configuration

Only the available options are displayed.
User settings are not protected by default. You can enable the password
through the User Password setting.
Table 4 describes the options that you can change.
S
P-164000005 Rev 2
Default Setting
English
Disabled
Enabled
01/01/2010
12:00:00
Enabled
9910-E35: 208V
9910-E36: 230V
9910-E66: Auto sensing
9910-E67: Auto sensing
NOTE When configured
for auto sensing, the
UPS uses the optimal
detected setting for
voltage.