Eaton Powerware 9910-E64 Handbook

Eaton Powerware 9910-E64 Handbook

Ibm system i and system p applications
Hide thumbs Also See for Powerware 9910-E64:

Advertisement

Power Protection Handbook for IBM System i and System p Applications
Powerware 9910 UPS
International
July 2008

Advertisement

Table of Contents
loading

Summary of Contents for Eaton Powerware 9910-E64

  • Page 1 Power Protection Handbook for IBM System i and System p Applications Powerware 9910 UPS International July 2008...
  • Page 2: Table Of Contents

    For the latest information, go to www.powerware.com/ibm. Eaton, Powerware, ABM, LanSafe, ConnectUPS, and X-Slot are trade names, trademarks and/or service marks of Eaton Corporation or its subsidiaries and affiliates. All other trademarks are property of their respective owners.
  • Page 3: Resources And Sales Tools On The Web: Powerware.com/Ibm

    Resources and Sales Tools on the Web: powerware.com/ibm ® The following information is available to you on the web or from your Eaton representative. Please note that the web site is updated more frequently than this handbook. Download the latest information from www.powerware.com/ibm.
  • Page 4: Power Problems And Their Ups Solutions

    9 Power Problems and Their UPS Solutions www.powerware.com/ibm +44 (0) 845 177 3410...
  • Page 5: Ups Topologies: Online, Line-Interactive, And Standby

    UPS. An online UPS uses the problems 4 – 9 (see page 5). battery less often than any other UPS technology, therefore increasing the life expectancy of the battery. Eaton’s robust, state-of-the-art online UPS provides superior protection for your communication and networking systems.
  • Page 6: Frequently Asked Questions

    Frequently Asked Questions What happens if the UPS is overloaded? For example, if the 11. How can you be sure UPS batteries are in good condition in protected equipment and/or load draws more current than order to insure they have maximum holdover in the event of the UPS can provide.
  • Page 7: Preventing Ups Problems

    If you have any review that site at which the UPS will be located. Here are a few questions about this information, please contact your Eaton general guidelines: consultant for IBM UPS sales.
  • Page 8: Rohs Compliant And Pre-Rohs Part Number Cross Reference Chart

    RoHS restricts the use of the following 6 substances: Lead, Mercury, Cadmium, Chromium VI (Also known as hexavalent chromium), PBB, PBDE Throughout 2006 Eaton updated our domestic and international products to meet RoHS and WEEE standards. As part of this process, most Powerware product part numbers were changed.
  • Page 9: Glossary Of Power Terms

    Glossary of Power Terms Ampere (A or Amp) – The unit of measure for the “rate of Electromagnetic Interference (EMI) – Electrical interference flow” of electricity, analogous to “gallons per minute.” that can cause equipment to work improperly. EMI can be VA x 0.7 (power factor) = Watts separated into conducted EMI (interference conducted through cables out of the UPS) and radiated EMI (interference...
  • Page 10 Glossary of Power Terms (continued) Maintenance bypass – An external wiring path to which the Relay Communication – Communication between a UPS and load can be transferred in order to upgrade or perform service a computer through the opening and closing of solid-state on the UPS without powering down the load.
  • Page 11: Commonly-Used Acronyms

    Commonly-Used Acronyms Advanced Battery Management SNMP Simple Network Management Protocol Alternating Current Total Harmonic Distortion Break-Before-Make (Bypass Switch) Underwriter’s Laboratory Bypass Distribution Module Uninterruptible Power System British Thermal Unit Universal Serial Bus Canadian Standards Association Volt Amps Direct Current VoIP Voice Over IP Extended Battery Cabinet Wide Area Network...
  • Page 12: Recommended Powerware 9910 Ups By Application

    Recommended Powerware 9910 UPS by Application Server (power draw) POWER Systems Power 520 (750W) 8204-E4A (AIX, Linux) 9407-M15 (IBM i, (i5/OS)) 9408-M25 (IBM i, (i5/OS)) Power 550 (1,100W) 8204-E8A (AIX, Linux) 9409-M50 (IBM i, (i5/OS)) Power 570 (Watts vary) 9117-MMA (AIX, Linux) 9406-MMA (IBM i, (i5/OS)) 2-4 core (up to 1400W) 5-8 core (up to 2800W)
  • Page 13: How Much Battery Runtime Do You Need

    How Much Battery Runtime Do You Need? To meet customer needs of continued operation during power outages, Powerware 9910 UPS solutions offer options that can extend battery runtimes beyond 60 minutes. In today's 24x7 business environment, continued availability along with application and safety considerations must be taken into account and estimated when calculating UPS battery runtimes.
  • Page 14: Attributes At A Glance

    Attributes at a Glance Attribute IBM Part Number 39J4810 39J4812 42R8069 42R8065 42R8073 42R8077 44V3923 Vac Input/Output 208-240 208-240 208-240 208-240 220-240 Maximum Output (Watts) 1050 2100 2700 4200 4500 8000 Maximum Output (VA) 1400 1500 3000 3000 6000 5000 10000 Level of Protection (Series) Tower Form Factor...
  • Page 15: Powerware 9910-P14

    Powerware 9910-P14 950 Watt/1400 VA, 230 Vac UPS Features and Benefits • Low cost power protection for entry- to mid-level desk side servers • Extends battery service life and provides advanced warning of the end of useful battery life with ABM technology •...
  • Page 16 P14 Technical Specifications* Electrical Input Nominal Voltage 230 Vac (user selectable to 220 Vac) Online Voltage Range ±20% for nominal voltage at full load Nominal Input Frequency 45–65 Hz, 50/60 Hz; auto-sensing Input Protection Reset-able circuit breaker Connection IEC-320-C14 Electrical Output Power Levels 950W/1400 VA Online Regulation...
  • Page 17 What’s Included with the P14 UPS • 950W/1400 VA, 230V UPS • Serial Cable, DB-9 to DB-9 (6 ft/1.8m) • AS/400 Interface Cable (6 ft/1.8m) • USB Cable, DB-9 to USB (6 ft/1.8m) • Powerware 5115 UPS User’s Guide • Powerware (9910-P13 and P14) Communication Options for IBM Applications Manual •...
  • Page 18: Powerware 9910-P16

    Powerware 9910-P16 1050 Watt/1500 VA, 230 Vac UPS Features and Benefits • Isolates connected equipment from all incoming power problems to provide the highest degree of protection with rugged, online design • Significantly increases battery service life and gives you advanced warning of the end of useful battery life with ABM technology •...
  • Page 19 P16 Technical Specifications* Electrical Input Nominal Voltage 230 Vac Input Voltage Ranges 150–288V (without using batteries) Input Power Factor >0.95 typical Frequency 50/60 Hz, auto-sensing Frequency Range 46–65 Hz Electrical Output On Utility Voltage Regulation ±3% of nominal On Battery Voltage Regulation ±3% of nominal Efficiency 89–92% depending on load...
  • Page 20 What’s Included with the P16 UPS • 1050W/1500 VA, 230V UPS • Powerware 9125 UPS User’s Guide • Powerware 9125 Installation Guide for IBM Applications • X-Slot Relay Interface Adapter Card User’s Guide • X-Slot RIA Quick Start Guide • AS/400 Interface Cable (6 ft/1.8m) •...
  • Page 21: Powerware 9910-E30

    Powerware 9910-E30 2100 Watt/3000 VA, 208-240 Vac UPS Features and Benefits • Isolates connected equipment from all incoming power problems to provide the highest degree of protection with rugged, online design • Conserves valuable rack space with compact 2U form factor •...
  • Page 22 What’s Included with the E30 UPS • 2100W /3000 VA, 208-240V UPS • E30 Accessory Kit (IBM Part Number 42R8070) - UPS Safety Manual - Powerware 9125 (2500–3000 VA) UPS User’s Guide - Powerware 9125 (9910 E30) Installation Guide for IBM Applications - Powerware Software Suite CD - Serial Cable, DB-9 to DB-9 (6 ft/1.8m) - Serial Cable, RJ-45 to DB-9 (6 ft/1.8m)
  • Page 23 E30 Technical Specifications* Electrical Input Nominal Voltage 208, 220, 230 and 240 Vac Input Voltage Ranges 160–288V (without using batteries) Input Power Factor >0.95 typical Frequency 50/60 Hz, auto-sensing Frequency Range 46–65 Hz Electrical Output On Utility Voltage Regulation ±3% of nominal On Battery Voltage Regulation ±3% of nominal Efficiency...
  • Page 24: Powerware 9910-E33

    Powerware 9910-E33 2700 Watt/3000 VA, 208-240 Vac UPS Features and Benefits • 0.9 power factor delivers more real output power in order to power more servers than another UPS of equivalent VA rating • Conservers valuable space with 2U rack height •...
  • Page 25 E33 Technical Specifications* Electrical Input Nominal Voltage 208, 220, 230, and 240 Vac Input Voltage Ranges 154–288V Frequency 50/60 Hz, auto-sensing Frequency Range 46–65 Hz Electrical Output On Utility Voltage Regulation -10% to +6% of nominal On Battery Voltage Regulation ±5% RMS Voltage Wave Shape (on battery Sine wave...
  • Page 26 What’s Included with the E33 UPS • 2700W/3000 VA, 208–240V UPS • E33 Accessory Kit (IBM Part Number 42R8066) • Powerware 5125 (2500–3000 VA) UPS User’s Guide • Powerware 5125 (9910 E33) Installation Guide for IBM Applications • (4) IEC-320-C13 to IEC-320-C14, 10A Equipment Power Cords (6 ft/1.8m) •...
  • Page 27: Powerware 9910-E64

    Powerware 9910-E64 4200 Watt/6000 VA, 208-240 Vac UPS Features and Benefits • Isolates connected equipment from all incoming power problems to provide the highest degree of protection with rugged, online design • Conservers valuable space with compact design • Significantly increases battery service life and gives you advanced warning of the end of useful battery life with ABM technology •...
  • Page 28 What’s Included with the E64 UPS • 4200W/6000 VA, 208–240V UPS • (2) UPS Internal Battery Trays (IBM Part Number 42R4316) • E64 Accessory Kit (IBM Part Number 42R8074) - UPS Safety Manual - UPS Lower Front Panel (Bezel) Black - Powerware 9125 (5000/6000 VA) UPS User’s Guide - Powerware 9125 (9910 E64) Installation Guide for IBM Applications - Powerware Software Suite CD...
  • Page 29 E64 Technical Specifications* Electrical Input Nominal Voltage 208, 220, 230, and 240 Vac Input Voltage Ranges 160–288V (without using batteries) Frequency 50/60 Hz, auto-sensing Input Power Factor >0.96 in any mode Frequency Range 50 Hz: 47–53 Hz; 60 Hz: 57–63 Hz Electrical Output On Utility Voltage Regulation ±3% of nominal...
  • Page 30 E64 Applications Matrix Various options are available depending on application. For System i or System p applications, consult chart below to select appropriate feature codes to order with the E64 UPS. POWER POWER POWER POWER POWER (AIX, (AIX, POWER (IBM i), (IBM i), (AIX, IBM Part...
  • Page 31: Powerware 9910-E65

    Powerware 9910-E65 4500 Watt/5000 VA, 208-240 Vac UPS Features and Benefits • High power, low profile design ideal for dense i5, p5, System i, System p and Power configurations • Supports multiple PDUs (1–3 PDUs in a non-redundant power configuration and 2–6 PDUs in a dual-redundant power configuration) •...
  • Page 32 E65 Technical Specifications* Electrical Input Nominal Voltage 200/208, 220, 230, and 240 Vac Input Voltage Ranges 160–288V Frequency 50/60 Hz, auto-sensing Frequency Range 46–54 Hz for 50 Hz; 56–64 Hz for 60 Hz Electrical Output On Utility Voltage Regulation -10% to +6% of nominal On Battery Voltage Regulation ±5% RMS Voltage Wave Shape (on battery...
  • Page 33 What’s Included with the E65 UPS • 4500W/5000 VA, 208–240V UPS • (2) Battery Trays (IBM Part Number 39J4828) • Accessory kit (IBM Part Number 42R8078) consisting of - UPS Front Panel (Bezel) Black - Powerware 5125 (5000/6000 VA) User’s Guide - Powerware 5125 (9910 E65) Installation Guide for IBM Applications - UPS Safety Manual - Powerware Software Suite CD...
  • Page 34: Powerware 9910-E83

    Powerware 9910-E83 8000 Watt/10000 VA, 220-240 Vac UPS Features and Benefits • High power, low profile design ideal for dense i5, p5 or Blades • System i, System p and Power configurations • Supports multiple PDUs (1–5 PDUs in a non-redundant power configuration and 2-10 PDUs in a dual-redundant power configuration) •...
  • Page 35 E83 Rear Panel What’s Included with the E83 UPS • 8000W/10000 VA, 220V nominal, optional 208, 230–240V UPS • (4) Battery Trays (IBM Part Number 44V3920) • (Internal) Accessory Kit (no IBM PN) - Mounting Brackets front and rear - Rails (left, right) and hardware •...
  • Page 36 E83 Technical Specifications* Electrical Input Nominal Voltage 220 default, optional; 200, 208, 230, and 240 Vac Input Voltage Ranges 220/230/240; 174-288V or 200/208; 160–253V, Frequency 50/60 Hz, auto-sensing Frequency Range 45-65Hz Default Frequency 60Hz Maximum Input Current at Nominal Utility Voltage Noise Filtering MOVs and line filter for normal and common mode noise Connections...
  • Page 37 Environmental and Safety Operating Temperature 0 to 40°C (32 to 104°F) Storage Temperature -20 to 50°C (-4 to 122°F) Relative Humidity 0% to 95% noncondensing Heat Dissipation 2066 BTU/hr (605.5W) maximum Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5 Surge Energy Rating High-energy 6500A peak Audible Noise...
  • Page 38: Powerware Software And Connectivity

    Powerware Software and Connectivity Power management software unifies and centralizes UPS management Bundled with every Powerware 9910 UPS, Powerware LanSafe power management software gives you control and visibility over all your UPS systems, using an intuitive, graphical interface and SNMP (Simple Network Management Protocol).
  • Page 39 ConnectUPS, and X-Slot are trade 8609 Six Forks Road names, trademarks and/or service Raleigh, NC 27615 U.S.A. marks of Eaton Corporation or its sub- Toll Free: 1.800.925.4426 sidiaries and affiliates. All other trade- or 919.872.3020 marks are property of their respective owners.

Table of Contents