OPERATION

Behavior on Overload

Table 5. Behavior on Overload (3000 VA Models)
Overload
Load
On Utility Power
Severity
Level
Level 1
100% to
Overload alarm only and support load
101%
indefinitely
Level 2
102% to
Shutdown in 2 minutes
110%
Level 3
>110%
Shutdown in 300 milliseconds
Table 6. Behavior on Overload (6000 VA Models)
Overload
Load
On Utility Power
Severity
Level
Level 1
100% to
Overload alarm only and
101%
support load indefinitely
Level 2
102% to
Transfer to Bypass after
110%
12 seconds (±1). If Bypass is
not available, transfer to Fault
mode after 12 seconds (±1)
Level 3
>110%
Transfer to Bypass
immediately. If Bypass is not
available, transfer to Fault
mode in 300 ms to 1 second
30
Eaton 9910 UPS and EBM User's Guide
Table 5 and Table 6 explain how the UPS responds to an overload
condition.
S
P-164000005 Rev 2
On Battery
Overload alarm only, support load until low
battery shutdown level is reached
Shutdown in 12 seconds or until low battery
shutdown level is reached
Shutdown in 2 seconds
On Bypass
Overload alarm only and
support load indefinitely
Overload alarm plus "Level 2
Overload" alarm only and
support load indefinitely
Overload alarm plus "Level 2
Overload" alarm plus "Level 3
Overload" alarm only and
support load indefinitely
On Battery
Overload alarm only, support
load until low battery
shutdown level is reached
Transfer to Fault mode after
12 seconds (±1) or until low
battery shutdown level is
reached
Transfer to Fault mode in
300 ms to 1 second