About Data Field Programming

The following pages list this control's data fields in numerical order. Field numbers are listed in the
left column, followed by a "Title and Data Entries column, which lists the valid entries for each field.
Experienced installers can simply follow this column when programming the data fields. The
"Explanation" column provides explanatory information and special notes where applicable.
Use the blank programming form to record the data for this installation.

Programming Data Fields

Data field programming involves making the appropriate entries for each of the data fields.
Start Data Field programming by entering the installer code + 8 + 0 + 0.
System Setup Fields ( ∗ 20 – ∗29)
FIELD
TITLE and DATA ENTRIES
Installer Code
*20
Enter 4 digits, 0-9
Quick Arm Enable
*21
0 = do not allow quick arm
1 = allow quick arm
RF Jam Option
*22
0 = no RF jam detection
1 = send RF jam report
Forced Bypass
*23
0 = no forced bypass
1 = automatically bypass all faulted zones
RF House ID Code
*24
00 = disable all wireless touchpad usage
01–31 = House ID for partition 1, 2 and
Chime By Zone [List]
*26
0 = no zone list (chimes on fault of any
entry/exit or perimeter zone when chime
mode on)
1 = use zone list (chimes on fault of
specific zones programmed in relay
zone list 3 when Chime mode on)
Powerline Carrier Device (X-10)
*27
House ID
0 = A
1 = B
2 = C
3 = D
4 = E
5 = F
Access Code for Phone Module
*28
1-9 = first digit of access code
∗ or # = second digit of access code (enter #
+11 for "∗", or # +12 for "#")
common
6 = G
# + 11 = L
7 = H
# + 12 = M
8 = I
# + 13 = N
9 = J
# + 14 = O
# + 10 = K
# + 15 = P

Data Field Programming

EXPLANATION
The Installer Code is used to assign the 4-digit Master Security Code.
See "Master Code" in the System Operation section for procedure.
If enabled, a user code is not needed to arm the system. Instead,
users can press the [#] followed by an arming key to arm the system.
However, the user code is always needed to disarm the system.
If enabled, a report is sent if the system detects an RF jamming
signal.
All zones bypassed by this function will be displayed after the bypass
is initiated. UL installations must be 0 (no forced bypass)
The House ID identifies receivers and wireless touchpads. If a 5827
or 5827BD Wireless Touchpad or 5804BD Transmitter is being used,
a House ID code must be entered, and the touchpad should be set to
the same House ID. You can assign RF house ID for each partition.
If enabled, you can define the specific zones intended to chime when
faulted while the system is in Chime mode. Use zone list 3 to assign
these zones (see ∗81 Zone List Programming section for details).
Powerline Carrier devices require a House ID, identified in this field.
Program Powerline Carrier devices in interactive modes ∗79, *80 and
*81.
You need to assign a 2-digit access code for the 4285/4286 Phone
Module, if used.
Example: If desired access code is 7∗ , 7 is the first entry, and [#] + 11
(for ∗) is the second entry.
NOTE: A "0" in either digit disables the phone module.