FIELD
TITLE and DATA ENTRIES
Long Range Radio Output
*29
0 = not used
1 = using Long Range Radio output
U L
Installations listed for UL must be 0
(Long Range Radio disabled).
Zone Sounds & Timing ( ∗ 31– ∗ 39)
FIELD
TITLE and DATA ENTRIES
Single Alarm Sounding Per Zone
*31
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming
period for a given zone
Fire Alarm Sounder Timeout
*32
0 = yes; fire sounder timeout after time
programmed in field ∗33
1 = no fire sounder timeout; continue
sounding until manually turned off
Alarm Sounder Timeout
*33
0 = No timeout
1 = 4 min
2 = 8 min
Exit Delay
*34
00-99 = Exit Delay time for each partition in
Entry Delay #1
*35
00-99 = Entry Delay time for each partition
Entry Delay 02
*36
00-99 = Entry Delay time for each partition
Audible Exit Warning
*37
0 = no exit warning sound
1 = provide exit warning sound when armed
Away
Confirmation Of Arming Ding
*38
0 = no ding
1 = confirmation ding after arming system
2 = confirmation ding after arming from RF
button or RF touchpad only
Power-Up In Previous State
*39
0 = always power-up in a disarmed state
1 = assume the system status prior to
power down
4-2
3 = 12 min
4 = 16 min
seconds
in seconds.
in seconds.
EXPLANATION
If selected, all messages programmed to go to the primary telephone
line receiver will also be sent to the connected 7720PLUS, 7820,
7835, or 7845 Radio (sent in Contact ID format). The data line is
supervised as well as certain functions in the radio. If
communication is lost or a trouble develops, an attempt will be made
to send a message via both radio and telephone to the central station.
Program the radio for device address 3.
EXPLANATION
UL installations must be 0 (no limit).
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses.
This field determines whether the external sounder will shut off
after time allotted, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1
The system waits the time entered before arming entry/exit zones. If
the entry/exit door is left open after this time expires, an alarm will
occur. Common zones use same delay as partition 1.
Upon entering, the system must be disarmed before the time entered
expires, otherwise it sounds an alarm. Common zones use same
delay as partition 1.
UL installations must be set for a maximum of 20 seconds.
Upon entering, the system must be disarmed before the time entered
expires, otherwise it sounds an alarm. Common zones use same
delay as partition 1.
UL installations must be set for a maximum of 20 seconds.
Warning sound consists of slow continuous beeps until last 5 seconds,
then it changes to fast beeps. The warning sound ends when exit
time expires.
Confirmation of arming is 1/2 second external sounder "ding."
If "1" selected, ding occurs when closing report is sent, or at the end
of Exit Delay.
If "2" selected, ding occurs upon reception of the wireless arming
command.
When the system powers up armed, an alarm will occur 1 minute
after arming if a zone is faulted.
Note that if the previous state was armed Away or Stay, the system
will not respond to sensor changes for 1 minute, which allows time
for sensors such as PIRs to stabilize.
UL installations: must be 1 (power-up in previous state)