Process Alarm Upper Upper Limit Value; Process Alarm Upper Lower Limit Value - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Programmable controllers
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Process alarm upper upper limit value

Set the upper upper limit value of the warning output function (process alarm).
Range
-32768 to +32767
The process alarm upperlower limit value setting range error (Error code: 1A4H) occurs when the condition
"Process alarm upper upper limit value  Process alarm upper lower limit value  Process alarm lower upper
limit value  Process alarm lower lower limit value" is not satisfied.
For details warning output function, refer to the following.
Page 36 Process alarm
Name
Process alarm upper upper limit
value

Process alarm upper lower limit value

Set the upper lower limit value of the warning output function (process alarm).
Range
-32768 to +32767
The process alarm upperlower limit value setting range error (Error code: 1A4H) occurs when the condition
"Process alarm upper upper limit value  Process alarm upper lower limit value  Process alarm lower upper
limit value  Process alarm lower lower limit value" is not satisfied.
For details warning output function, refer to the following.
Page 36 Process alarm
Name
Process alarm upper lower limit
value
Connection part
Special register
CH1
1st adapter
SD6311
2nd adapter
SD6671
3rd adapter
SD7031
4th adapter
SD7391
Connection part
Special register
CH1
1st adapter
SD6312
2nd adapter
SD6672
3rd adapter
SD7032
4th adapter
SD7392
CH2
CH3
SD6351
SD6391
SD6711
SD6751
SD7071
SD7111
SD7431
SD7471
CH2
CH3
SD6352
SD6392
SD6712
SD6752
SD7072
SD7112
SD7432
SD7472
2.13 Detail of Special Registers
Default value
R/W
0
R/W
CH4
SD6431
SD6791
SD7151
SD7511
Default value
R/W
0
R/W
CH4
SD6432
SD6792
SD7152
SD7512
2 FX5-4AD-ADP
85
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents