D/A Conversion Enable/Disable Function; D/A Output Enable/Disable Setting Function - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Programmable controllers
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

D/A Conversion Enable/Disable Function

The output range of the analog output can be switched for each channel.
Setting methods
Set "D/A conversion enable/disable setting" to "D/A conversion enable" or "D/A conversion disable".
Navigation window  [Parameter]  [Module Information]  Module model name  [Module Parameter]  "Basic
Settings"  "D/A Conversion Enable/Disable Setting"
Corresponding devices
The devices which are used by the D/A conversion enable/disable function are listed below.
Name
D/A conversion enable/disable setting
Operation
The digital value is D/A-converted only in the channels for which the "D/A conversion enable/disable setting" is set to "enable".
The channels for which the "D/A output enable/disable setting" is set to "enable" output the converted analog value.
When the "D/A conversion enable/disable setting" is changed from "enable" to "disable", the digital value is held as is, and the
digital operation value and analog output value monitor are cleared.

D/A Output Enable/Disable Setting Function

Specify whether to output the D/A conversion value or offset value for each channel.
The conversion speed is a constant, regardless of the output enable/disable state.
Setting methods
Set "D/A output enable/disable setting" to "D/A output enable" or "D/A output disable".
Navigation window  [Parameter]  [Module Information]  Module model name  [Module Parameter]  "Basic
Settings"  "D/A Output Enable/Disable Setting"
Corresponding devices
The devices which are used by the D/A output enable/disable setting function are listed below.
Name
D/A output enable/disable setting
Operation
The channels for which the "D/A output enable/disable setting" is set to "enable" output the analog value D/A-converted from
the digital value.
The channels for which the "D/A output enable/disable setting" is set to "disable" output the offset value.
CH1
CH2
SM6300
SM6340
CH1
CH2
SM6301
SM6341
CH3
CH4
SM6380
SM6420
CH3
CH4
SM6381
SM6421
3
Reference
Page 129
Reference
Page 129
3 FX5-4DA-ADP
101