D/A Conversion Error Flag - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Programmable controllers
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

D/A conversion error flag

"D/A conversion error flag" turns on when an error occurs.
Monitor value
0: OFF
1: ON
To turn OFF the "D/A conversion error flag" and clear the "D/A conversion latest error code", set the "error clear request"
(SM50) of the CPU module from OFF to ON.
D/A conversion
latest error code
D/A conversion
error flag
Error clear request (SM50)
Name
D/A conversion error flag
3 FX5-4DA-ADP
134
3.11 Detail of Special Relays
Display description
Normal
D/A conversion error occur
0
ON
OFF
ON
OFF
Connection part
Special relay
CH1
1st adapter
SM6339
2nd adapter
SM6699
3rd adapter
SM7059
4th adapter
SM7419
Error occur
0
CH2
SM6379
SM6739
SM7099
SM7459
Default value
0: OFF
CH3
CH4
SM6419
SM6459
SM6779
SM6819
SM7139
SM7179
SM7499
SM7539
R/W
R

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents