List Of Special Registers; Special Registers For Analog Input; Special Registers For Analog Output - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Programmable controllers
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

4.11

List of Special Registers

This section describes the special registers used for analog input and output.

Special registers for analog input

Special registers
CH1
SD6020
SD6021
SD6022
SD6023
SD6024
SD6026
SD6027
SD6028
SD6029
SD6030
SD6031
SD6032
SD6033
SD6034
SD6058
SD6059
R/W: Read/Write
R: Read only

Special registers for analog output

Special registers
SD6180
SD6181
SD6182
SD6183
SD6184
SD6188
SD6189
SD6190
SD6191
SD6192
SD6218
SD6219
R/W: Read/Write
R: Read only
CH2
SD6060
SD6061
SD6062
SD6063
SD6064
SD6066
SD6067
SD6068
SD6069
SD6070
SD6071
SD6072
SD6073
SD6074
SD6098
SD6099
Description
Digital output value
Digital operation value
Analog input voltage monitor
Average processing specify
Time Average/Count Average/Moving Average setting
Maximum value
Minimum value
Scaling upper limit value
Scaling lower limit value
Conversion value shift amount
Process alarm upper upper limit value
Process alarm upper lower limit value
Process alarm lower upper limit value
Process alarm lower lower limit value
A/D Conversion latest alarm code
A/D Conversion latest error code
Description
Digital value
Digital operation value
Analog output voltage monitor
HOLD/CLEAR function setting
HOLD setting value
Scaling upper limit value
Scaling lower limit value
Input value shift amount
Warning output upper limit value
Warning output lower limit value
D/A conversion latest alarm code
D/A conversion latest error code
4 FX5U CPU MODULE BUILT-IN ANALOG
R/W
R
R
R
R/W
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R/W
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R