External Power Supply Disconnection Detection Function; Disconnection Detection Function - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Programmable controllers
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Set the warning output upper limit value and warning output lower limit value while satisfying the condition
"Warning output upper limit value>Warning output lower limit value".
Corresponding devices
The devices which are used by the alarm output function are listed below.
Name
Warning output upper limit value flag
Warning output lower limit value flag
Warning output setting
Warning output upper limit value
Warning output lower limit value

External Power Supply Disconnection Detection Function

This function detects that the external power (24 V DC) is not supplied to the FX5-4DA-ADP or the supply is stopped.
Setting procedure
The user does not need to configure any settings.
Operation
The error occurs when the external power is not input. (Error code: 3081H)

Disconnection Detection Function

Disconnection can be detected in each channel.
This function is enabled when the analog output range is 4 to 20 mA.
Setting procedure
1.
Set "Disconnection detection enable/disable setting" to "Enable".
Navigation window  [Parameter]  [Module Information]  Module model name  [Module Parameter]  "Application
Settings"  "Disconnection detection enable/disable setting"
2.
Set "Disconnection recovery detection enable/disable setting".
Navigation window  [Parameter]  [Module Information]  Module model name  [Module Parameter]  "Application
Settings"  "Disconnection recovery detection enable/disable setting"
Corresponding devices
The devices which are used by the disconnection detection function are listed below.
Name
Disconnection detection flag
Disconnection detection enable/disable setting
Disconnection recovery detection enable/
disable setting
Operation
When disconnection is detected in a channel for which the "D/A conversion enable/disable setting" is set to "D/A conversion
enable" and the "disconnection detection enable/disable setting" is set to "enable", it is regarded as a disconnection detection
error, and the "disconnection detection flag" turns ON (Error code: 1BB).
At this time, the digital value, digital operation value and analog output value monitor are cleared.
When the "disconnection recovery detection enable/disable setting" is set to "enable", the "disconnection detection flag" turns
OFF when the channel is recovered from disconnection.
3 FX5-4DA-ADP
108
3.3 Functions
CH1
CH2
SM6311
SM6351
SM6312
SM6352
SM6313
SM6353
SD6311
SD6351
SD6312
SD6352
CH1
CH2
SM6318
SM6358
SM6319
SM6359
SM6320
SM6360
CH3
CH4
SM6391
SM6431
SM6392
SM6432
SM6393
SM6433
SD6391
SD6431
SD6392
SD6432
CH3
CH4
SM6398
SM6438
SM6399
SM6439
SM6400
SM6440
Reference
Page 130
Page 130
Page 131
Page 140
Page 140
Reference
Page 131
Page 131
Page 132