Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 23

Programmable controllers
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Current input characteristic
The following shows the list of the analog input ranges and the graph of each current input characteristic, at the current input.
No.
Input range setting
(1)
0 to 20 mA
(2)
4 to 20 mA
(3)
-20 to +20 mA
*1 When analog input exceeds the range of the digital output value, the digital output value is fixed to the maximum or minimum.
Input range setting
0 to 20 mA
4 to 20 mA
-20 to +20 mA
• Set values within the practical range of the analog input and digital output at each input range. If the values
are out of the range, the resolution and accuracy may not fall within the range of the performance
specifications. (Do not use values in the dotted line region in the graph of current input characteristics.)
• Do not set the voltage over 30 mA. Doing so can cause breakdown of the products.
■Current input characteristics graph (0 to 20 mA)
Practical analog input range
16383
16000
Digital
0
output
-384
value
-16000
-16383
-40
-20
Analog input current (mA)
■Current input characteristics graph (4 to 20 mA)
Practical analog input range
13183
12800
Digital
0
output
-3584
value
-12800
-40
-20
Analog input current (mA)
Offset value
Gain value
0 mA
20 mA
4 mA
20 mA
0 mA
20 mA
Digital output value
Minimum
-384
-3584
-8129
-0.48
0
20 20.48 40
-0.48 4
20 20.48 40
*1
Digital output value
0 to 16000
0 to 12800
-8000 to +8000
Maximum
16383
13183
8191
2 FX5-4AD-ADP
2.1 Specifications
Resolution
1.25 A
2
1.25 A
2.5 A
21