Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 99

Programmable controllers
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Current output characteristic
The following shows the list of the analog output ranges and the graphs of each current output characteristic, at the current
output.
No.
Output range setting
(1)
0 to 20 mA
(2)
4 to 20 mA
*1 When value exceeds the range of the digital value, the digital value is fixed to the maximum or minimum.
Output range setting
0 to 20 mA
4 to 20 mA
Set values within the practical range of the digital input and analog output at each output range. If the values
are out of the range, the resolution and accuracy may not fall within the range of the performance
specifications. (Do not use values in the dotted line region in the graph of current output characteristics.)
■Current output characteristics graph (0 to 20 mA)
40
20.48
20
Analog
output
0
current
-0.48
(mA)
-20
-40
-16000
■Current output characteristics graph (4 to 20 mA)
40
20.38
20
Analog
4
output
3.62
current
0
(mA)
-20
-40
-16000
Offset value
Gain value
0 mA
20 mA
4 mA
20 mA
Digital value
Minimum
-384
-384
-384
0
16000 16383
Digital value
-384
0
16000 16383
Digital value
*1
Digital value
0 to 16000
0 to 16000
Maximum
16383
16383
Practical analog
output range
Practical analog
output range
Resolution
1.25 A
1 A
3
3 FX5-4DA-ADP
97
3.1 Specifications

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents