Analog Output Test when CPU Module is in STOP Status Function

Outputs a user-defined analog value by setting the output enable/disable flag to enabled and changing the digital value, when
the CPU module is stopped.
Corresponding devices
The devices that are used by analog test function when the CPU module is stopped are listed below.
Name
D/A conversion enable/disable setting
D/A output enable/disable setting
Digital value
Setting methods
The procedure to use the analog test function is described below.
1.
Change the operation conditions setting.
The following conditions must be satisfied to enable the analog output test.
Description
D/A conversion enable/disable
D/A output enable/disable
2.
Update the digital value.
Set the digital value corresponding to the analog value desired to be output as a digital value.
Operation
The digital input value will be converted to an analog signal and output regardless of whether the CPU module in the RUN
state or STOP state.
The settings for the shift function, scaling function, and warning output function are valid during the analog output test.
Precautions
Even when the analog output HOLD/CLEAR function is operating, analog output can be changed by this function.
CH1
SM6180
SM6181
SD6180
Setting value
Conversion enabled
Output enabled
4 FX5U CPU MODULE BUILT-IN ANALOG
4.4 Functions (Analog output)
4
157