9.2

DIP Switch Configuration

DIP switches 1 and 2 are used to select the unit's responder address. Switches 3-5, and 7 are reserved and set to
the OFF position. DIP switch 8 when set to ON will reset all DCPx configuration settings back to default, this
switch should be set to the OFF position.
9.3

Baud Rate Selection

The baud rate is selected using DIP switch 6.
0 = 2400
1 = 4800
9.4

Enable DIP Switch Configuration

Use DIP switch 8 to enable your DIP switch configuration.
Note: When DIP switches are being used, and are enabled with switch 8, all system alarms are disabled except
for the "DIP Switch Configuration" Alarm.
10

Operations

10.1

Front and Rear Panel LEDs

The six bicolor LEDs on the front panel of the NetGuardian 480 provide visual feedback of communication,
configuration, and alarm status.
The CRF LED displays communication over the secondary Craft port. CRF will BLINK GREEN when the
NetGuardian 480 is TRANSMITTING data, and BLINK RED when the NetGuardian 480 is RECEIVING data.
The SER LED displays communication over the primary serial port. CRF will BLINK GREEN when the
NetGuardian 480 is TRANSMITTING data, and BLINK RED when the NetGuardian 480 is RECEIVING data.
Table. E. DIP switch positions
Fig. 48. Front panel LED display.
40