8 Configuration
#
Code
[A.2.1.9]
[F-0D]
<< continuation
▪ 1 (Sample)(default): The pump is ON
when there is heating demand and the
leaving water temperature has NOT
reached the desired temperature yet.
When thermo OFF condition occurs,
the pump runs every 5  minutes to
check the water temperature and
demand
Remark: Sample is NOT available in
external room thermostat control or
room thermostat control.
a
b
d
g
b
▪ a: Space heating control (user
▪ b: OFF
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
#
Code
[A.2.1.9]
[F-0D]
<< continuation
▪ 2 (Request): Pump operation based
on request. Example: Using a room
thermostat creates thermo ON/OFF
condition. When there is no such
demand, the pump is OFF. Remark:
Request is NOT available in leaving
water temperature control.
a
b
d
e
b
▪ a: Space heating control (user
▪ b: OFF
▪ c: On
▪ d: Heating demand (by ext RT or
▪ e: Pump operation
Brine freezing temperature
Depending on the type and concentration of the anti-freeze in the
brine system, the freezing temperature will differ. The following
parameters set the units freeze up prevention limit temperature. To
allow
for
temperature
measurement
concentration MUST resist to a lower temperature than the defined
setting.
Installer reference guide
38
Description
heating
if
necessary.
c
e
f
c
interface)
continued >>
Description
c
c
b
c
interface)
RT)
tolerances,
the
General rule: the units freeze up prevention limit temperature MUST
be 10°C lower than the minimum possible brine inlet temperature for
the unit.
Example: When the minimum possible brine inlet temperature in a
certain application is 0°C, then the unit freeze up prevention limit
temperature MUST be set to –10°C or lower. Result will be that the
brine mixture may NOT freeze above that temperature. To prevent
freezing of the unit, check the type and concentration of the brine
carefully.
#
Code
[A.6.9]
[A‑04]
NOTICE
The setting brine freezing temperature can be modified
and the read out is correct in [A.6.9] Brine freezeup temp
ONLY after having accessed menu [A.8] Overview
settings.
This setting can ONLY be modified and/or saved and the
read out is ONLY correct if the communication between
hydro module and compressor module is present. The
communication between hydro module and compressor
module is NOT guaranteed and/or applicable if:
▪ error "U4" appears on the user interface,
▪ the heat pump module is connected to preferential kWh
rate power supply where power supply is interrupted
and preferential kWh rate power supply is activated.
Capacity boost
For systems where higher capacity is required, the compressor
frequency can be increased. Remark that higher capacity results in
higher sound level.
#
Code
N/A
[A‑03]
8.2.3

Quick wizard: Options

Domestic hot water settings
Following settings must be made accordingly.
#
Code
N/A
[E-05]
brine
Description
Brine freezeup temp
▪ 0: 0°C
▪ 1: –2°C
▪ 2: –4°C
▪ 3: –6°C
▪ 4: –8°C
▪ 5: –10°C
▪ 6: –12°C
▪ 7 (default): –14°C
Description
Compressor frequency
▪ 0 (default): normal
▪ 1: boost
Description
DHW operation:
▪ 0 (No): N/A
▪ 1 (Yes): Installed. Do NOT change this
setting.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02