Quick wizard: Language / time and date..... 15 Daikin website (publicly accessible). 5.2.2 Quick wizard: Standard..........15 ▪ The full set of latest technical data is available on the Daikin 5.2.3 Quick wizard: Options ..........15 extranet (authentication required). 5.2.4 Quick wizard: Capacities (energy metering) ....
See the installer reference guide for more information. Minimum required flow rate during backup heater operation 12 l/min See the recommended procedure as described in "6.2 Checklist during commissioning" on page 20. Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
To open the indoor unit 1 Loosen and remove the screws at the bottom of the unit. 2 Push on the button at the bottom of the front plate. EGSQH10S18AA9W Installation manual Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
7 Adjust the height of the 2 front leveling feet of the inner frame to compensate for irregularities. CAUTION Check that the heat pump module does NOT touch the outer casing. Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
The piping in the complete brine circuit MUST be insulated to can become negative. It MUST be protected against prevent reduction of the heating capacity. freezing. Refer to setting [A‑04] in "5.2.2 Quick wizard: Standard" on page 15. EGSQH10S18AA9W Installation manual Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
≥50 mm 2 Wiring should enter the unit from the top: ≥50 mm 3 Routing of the wiring inside the unit should be as follows: ≥ 5 0 EGSQH10S18AA9W Installation manual Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
In case of normal kWh rate power supply X19A X19A 30 31 X6YB X6YB X6YA X6Y X6YA Main power supply Legend: see illustration below. Normal kWh rate power supply Preferential power supply contact Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
4A From the rear 4B From the left in the room (used as room thermostat). The procedure differs slightly depending on where you install the user interface. 1× 1× EGSQH10S18AA9W Installation manual Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
1 Connect the electrical meters cable to the appropriate terminals as shown in the illustration below. Installation of EKRP1HB is required. 2 Fix the cable with cable ties to the cable tie mountings. Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
1 Make sure that the front panel is removed from the indoor unit. "4.1.1 To open the indoor unit" on page 5. 2 Plug the user interface cover into the hinges. EGSQH10S18AA9W Installation manual Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
You can access the installer settings using two different methods. However, NOT all settings are accessible via both methods. If so, the corresponding table columns in this chapter are set to N/A (not applicable). Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
Minimum leaving water temperature setpoint required to reach a stable condition on the comfort setpoint for the ▪ T : Target leaving water temperature room. (additional) ▪ T : Outdoor temperature EGSQH10S18AA9W Installation manual Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
Power consumption control NOTICE During periods of excessive capacity demand (example: screed dryout function), the power limitation can be activated in accordance to the dimension of the brine earth collector. Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
Power saving settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings, settings will be visible/invisible. EGSQH10S18AA9W Installation manual Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
– the installer returns to the site, the installer NOTICE has to set [4‑0E] to "1" manually. It is required that the brine circuit is filled BEFORE the brine pump test run is activated. Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
Once the test run is finished and the unit operates properly, please make sure the following is clear for the user: ▪ Fill in the installer setting table (in the operation manual) with the actual settings. Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
8 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin extranet (authentication required). Piping diagram: Indoor unit...
Page 25
(voltage supplied by PCB) Max. load Maximum load Only for brine pressure switch Only for brine pressure switch connection kit connection kit Normally closed Normally closed Switch box Switch box EGSQH10S18AA9W Installation manual Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
Page 26
Optional part Only for *KRUCBL* 2 core 2x0.75 A2P: P1-P2 user interface Note: communication - In case of signal cable: keep minimum distance to power cables >5 cm 4D081378-1B Installation manual EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351747-1F – 2016.06...
Page 28
4P351747-1 F 00000002 4P351747-1F 2016.06...