8 Configuration
7 Confirm the selection on the screen by pushing
(languages, schedules etc.) will be synchronised from the
selected source user interface to the other one.
INFORMATION
▪ During the copying, both controllers will NOT allow
operation.
▪ The copy operation can take up until 90 minutes.
▪ It is recommended to change installer settings, or the
configuration of the unit, on the main user interface. If
not, it can take up to 5 minutes before these changes
are visible in the menu structure.
8 Your system is now set to be operated by the 2 user interfaces.
8.1.4
To copy the language set from the first to
the second user interface
See
"8.1.3 To copy the system settings from the first to the second
user interface" on
page 35.
8.1.5
Quick wizard: Set the system layout after
first power ON
After first power ON of the system, you are guided on the user
interface to do initial settings:
▪ language,
▪ date,
▪ time,
▪ system layout.
By confirming the system layout, you can proceed with the
installation and commissioning of the system.
1 At power ON, the quick wizard starts as long as the system
layout was NOT confirmed yet, by setting the language.
Language
Select the desired language
Confirm
Adjust
2 Set the current date and time.
Date
What is the date today?
Tue
1
Jan
2013
Confirm
Adjust
Scroll
Time
What is the current time?
00
: 00
Confirm
Adjust
Scroll
3 Set the system layout settings: Standard, Options, Capacities.
For more details, see
"8.2 Basic configuration" on
Installer reference guide
36
and all data
A.2
Standard
Options
Capacities
Confirm layout
Select
4 After configuration, select Confirm layout and press
Please confirm the system
layout. The system will
restart and will be ready for
first startup.
OK
Confirm
5 The user interface re-initialises and you can proceed the
installation by setting the other applicable settings and
commissioning of the system.
When the installer settings are changed, the system will request to
confirm. When confirmation is complete, the screen will shortly turn
OFF and "busy" will be displayed for several seconds.
8.2
8.2.1
#
[A.1]
[1]
8.2.2
Space heating settings
The system can heat up a space. Depending on the type of
application, the space heating must be made accordingly.
#
[A.2.1.7]
page 36.
1
System layout
Scroll
Confirm layout
Cancel
Adjust

Basic configuration

Quick wizard: Language / time and date

Code
Description
N/A
Language
N/A
Time and date

Quick wizard: Standard

Code
Description
[C-07]
Unit control method:
▪ 0
(LWT
operation is decided based on the
leaving water temperature regardless
the actual room temperature and/or
heating demand of the room.
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat or
equivalent (e.g. heat pump convector).
▪ 2 (RT control): Unit operation is
decided
based
temperature of the user interface.
Daikin Altherma ground source heat pump
.
control)(default):
Unit
on
the
ambient
EGSQH10S18AA9W
4P351748-1D – 2016.02