5.2.2

Quick wizard: Standard

Space heating/cooling settings
#
Code
[A.2.1.7]
[C-07]
Unit temperature control:
▪ 0 (LWT control): Unit operation is
decided based on the leaving water
temperature.
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat.
▪ 2 (RT control): Unit operation is
decided
temperature of the user interface.
[A.2.1.8]
[7-02]
Number of water temperature zones:
▪ 0 (1 LWT zone): Main
▪ 1 (2 LWT zones): Main + additional
[A.2.1.9]
[F-0D]
Pump operation:
▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or
OFF condition.
▪ 1
condition occurs, the pump runs every
5  minutes and the water temperature
is checked. If the water temperature is
below target, unit operation can start.
▪ 2 (Request): Pump operation based
on request. Example: Using a room
thermostat and thermostat creates
thermo ON/OFF condition.
[A.2.1.B]
N/A
Only if there are 2 user interfaces:
User interface location:
▪ At unit
▪ In room
[A.2.1.C]
[E-0D]
Glycol present:
▪ 0 (No)(default)
▪ 1 (Yes)
5.2.3

Quick wizard: Options

External domestic hot water pump
#
Code
[A.2.2.A]
[D-02]
Domestic hot water pump:
▪ 0 (No): NOT installed
▪ 1 (Secondary rtrn): Installed for instant
hot water
▪ 2
disinfection
See also illustrations below.
Domestic hot water pump installed for...
Instant hot water
h
b
c
a
f
g
a
Outdoor unit
EBLQ+EDLQ05+07CAV3
Daikin Altherma low temperature monobloc
4P403578-1C – 2016.02
Description
based
on
the
ambient
(Sample):
When
thermo
OFF
Description
(Disinf.
shunt):
Installed
Disinfection
h
b
c
a
d
e
b
Tank
c
Domestic hot water pump
d
Heater element
e
Non‑return valve
f
Shower
g
Cold water
h
Control box
Remote outdoor sensor
#
Code
[A.2.2.B]
[C-08]
INFORMATION
You can only connect either the remote indoor sensor or
the remote outdoor sensor.
Control box EKCB07CAV3
#
Code
[A.2.2.E.1]
[E‑03]
[A.2.2.E.2]
[5-0D]
The system allows for the connection of 2 types of backup heater
kits:
▪ EKMBUHCA3V3: 1~ 230 V - 3 kW backup heater
▪ EKMBUHCA9W1: Unified backup heater
Backup heater EKMBUHCA3V3 can only be configured to be a 3V3
backup heater. Unified backup heater EKMBUHCA9W1 can be
configured in 4 ways:
▪ 3V3: 1~ 230 V, 1 step of 3 kW
▪ 6V3: 1~ 230 V, 1st step = 3 kW, 2nd step = 3+3 kW
▪ 6W1: 3N~ 400 V, 1st step = 3 kW, 2nd step = 3+3 kW
▪ 9W1: 3N~ 400 V, 1st step = 3 kW, 2nd step = 3+6 kW
To configure the backup heater (both EKMBUHCA3V3 and
EKMBUHCA9W1), combine settings [E‑03] and [5‑0D]:
for
Backup heater
configuration
3V3
6V3
6W1
9W1
#
Code
[A.2.2.E.4]
[E-05]
f
g
5 Configuration
Description
External sensor (outdoor):
▪ 0 (No): NOT installed.
▪ 1 (Outdoor sensor): Remote outdoor
sensor, connected to the outdoor unit.
▪ 2 (Room sensor): Remote indoor
sensor, connected to option box
EK2CB07CAV3.
Description
Backup heater steps:
▪ 0 (default)
▪ 1
▪ 2
BUH type:
▪ 1 (1P,(1/1+2)): 6  kW 1~  230  V
(default)
▪ 4 (3PN,(1/2)): 6 kW 3N~ 400 V (*9W)
▪ 5 (3PN,(1/1+2)): 9  kW 3N~  400  V
(*9W)
[E-03]
[5-0D]
1
1 (1P,(1/1+2))
2
1 (1P,(1/1+2))
2
4 (3PN,(1/2))
2
5 (3PN,(1/1+2))
Description
DHW operation:
Can the system prepare domestic hot
water?
▪ 0 (No): NOT installed
▪ 1 (Yes): Installed
Installation manual
13