Technical Specifications; Technical Specifications: Indoor Unit - Daikin EGSQH10S18AA9W Installer's Reference Manual

Altherma ground source heat pump
Hide thumbs Also See for EGSQH10S18AA9W:
Table of Contents

Advertisement

14.6

Technical specifications

14.6.1

Technical specifications: Indoor unit

Nominal capacity and nominal input
Indoor unit
(a)
Condition 1
Heating capacity
Power input
COP
(b)
Condition 2
Heating capacity
Power input
COP
(a)
Entering water temperature (brine)/leaving water temperature (brine) 0°C/3°C – leaving water condenser 35°C (DT=5°C).
(b)
Entering water temperature (brine)/leaving water temperature (brine) 0°C/3°C – leaving water condenser 45°C (DT=5°C).
Technical specifications
Indoor unit
Casing
Colour
Material
Dimensions
Packing (H×W×D)
Unit (H×W×D)
Weight
Machine weight
Gross weight
Packing
Material
Weight
PED
Category of unit
Most critical part
Main components
Water pump
Water side heat exchanger
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02
Minimum
Nominal
Maximum
Nominal
Nominal
Minimum
Nominal
Maximum
Nominal
Nominal
Ps*V
Ps*DN
Type
Nr. of speeds
(a)
Nominal ESP
Heating
pump
(b)
Heating
Power Input
Type
Quantity
Water volume
Minimum water flow rate
(a)
Nominal water
Heating
flow rate
(b)
Heating
Maximum water
Heating
flow rate
Insulation material
14 Technical data
Heating only
3.11 kW
10.20 kW
13.00 kW
2.34 kW
4.35
2.47 kW
9.29 kW
11.90 kW
2.82 kW
3.29
Heating only
White
Precoated sheet metal
1930×700×840 mm³
1732×600×728 mm³
210 kg
222 kg
Wood, carton, PE wrapping foil
12 kg
Category I
Compressor
135 bar
DC motor
Inverter controlled
39 kPa
46 kPa
70 W
Brazed plated
1
2.30 l
8.0 l/min
29.2 l/min
26.6 l/min
43.0 l/min
Green felt
Installer reference guide
79

Advertisement

Table of Contents
loading

Table of Contents