Heat Source Settings - Daikin EGSQH10S18AA9W Installer's Reference Manual

Altherma ground source heat pump
Hide thumbs Also See for EGSQH10S18AA9W:
Table of Contents

Advertisement

CAUTION
The disinfection function settings MUST be configured by
the installer according to the applicable legislation.
#
Code
[A.4.4.2]
[2-00]
Operation day:
▪ 0: Each day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5 (default): Friday
▪ 6: Saturday
▪ 7: Sunday
[A.4.4.1]
[2-01]
Disinfection
▪ 0: No
▪ 1 (default): Yes
[A.4.4.3]
[2-02]
Start time: 00~23:00 (default: 23:00),
step: 1:00.
[A.4.4.4]
[2-03]
Temperature target: 60°C (fixed).
[A.4.4.5]
[2-04]
Duration: 40~60 minutes, default: 40
minutes.
T
DHW
[2-03]
T
H
T
U
00.00
01.00
22.00
T
Domestic hot water temperature
DHW
T
User set point temperature
U
T
High set point temperature [2-03]
H
t
Time
WARNING
Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.
When the high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to the applicable legislation.
CAUTION
Be sure that the disinfection function start time [A.4.4.3]
with defined duration [A.4.4.5] is NOT interrupted by
possible domestic hot water demand.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02
Description
[2-04]
23.00
24.00
t
[2-02]
INFORMATION
In case of error code AH and no interruption of the
disinfection function occurred due to domestic hot water
tapping, following actions are recommended:
▪ When the Domestic hot water > Type > Reheat or
Reheat + sched. is selected, it is recommended to
program the start-up of the disinfection function at least
4  hours later than the last expected large hot water
tapping. This start-up can be set by installer settings
(disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is selected, it is recommended to program a Storage
eco 3  hours before the scheduled start-up of the
disinfection function to preheat the tank.
INFORMATION
Disinfection function is restarted in case the domestic hot
water temperature drops 5°C below the disinfection target
temperature within the duration time.
INFORMATION
An AH error occurs if you do the following during
disinfection:
▪ Set the user permission level to Installer.
▪ Go to the DHW tank temperature home page (Tank).
▪ Press
to interrupt the disinfection.
8.3.3

Heat source settings

Backup heater
Backup heater operation mode: defines when backup heater
operation is disabled, enabled or only allowed during domestic hot
water operation. This setting is only overruled when backup heating
is required during malfunctioning of the heat pump (when [A.5.1.2] is
set on manual or automatic).
#
Code
[A.5.1.1]
[4‑00]
Backup heater operation:
▪ 0: Disabled
▪ 1 (default): Enabled
[A.5.1.3]
[4‑07]
Defines whether backup heater second
step is:
▪ 1 (default): Allowed
▪ 0: NOT allowed
In this way it is possible to limit the
backup heater capacity.
N/A
[5‑00]
Is backup heater operation allowed
above equilibrium temperature during
space heating operation?
▪ 1 (default): NOT allowed
▪ 0: Allowed
[A.5.1.4]
[5‑01]
Equilibrium temperature.
Outdoor temperature below which
operation of the backup heater is
allowed.
Range: –15°C~35°C (default: 0°C) (step:
1°C)
8 Configuration
Description
Installer reference guide
49