Make sure installation, testing and applied materials 14.6.1 Technical specifications: Indoor unit ......79 comply with applicable legislation (on top of the 14.7 Operation range ................ 82 instructions described in the Daikin documentation). 14.7.1 Operation range: Indoor unit ........82 14.8 ESP curve ................. 84 CAUTION 14.8.1...
Corrosion of copper pipes or soldered parts may cause "Liquid filling siphon attached") the refrigerant to leak. 1.2.3 Refrigerant If applicable. See the installation manual or installer reference guide of your application for more information. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
If applicable. See the installation manual or installer reference guide of the earth leakage protector. of your application for more information. NOTICE Make sure water quality complies with EU directive 98/83 EC. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Latest revisions of the supplied documentation may be available on ▪ When connecting wiring which is the same thickness, the regional Daikin website or via your dealer. do as shown in the figure below. The original documentation is written in English. All other languages are translations.
4 Reinstall the top panel. ▪ room thermostat functionality in the principal space to be heated. ▪ To have an interface containing other languages. Following user interfaces are available: EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
NOTICE RTRNETA). Thermostat RTRNETA can only be used in heating-only systems. Daikin recommends to use a mechanical brine pressure switch. If an electrical brine pressure switch is used, For installation instructions, see the installation manual of the room capacitive currents might disturb the flow switch operation thermostat and addendum book for optional equipment.
Number of water temperature 0 (1 LWT zone): Main ▪ How many rooms are heated by the Daikin heat pump system? zones: ▪ Which heat emitter types are used in each room and what is their ▪ #: [A.2.1.8] design leaving water temperature? ▪...
Benefits 5.2.2 Multiple rooms – One LWT zone ▪ Wireless. The Daikin external room thermostat is available in a wireless version. If only one leaving water temperature zone is needed because the design leaving water temperature of all heat emitters is the same, ▪...
Page 11
External room thermostat INFORMATION Bypass valve To increase comfort and performance, Daikin recommends ▪ For each room, a shut-off valve (field supplied) is installed to avoid to install the valve kit option EKVKHPC on each heat pump leaving water supply when there is no heating demand.
Remote controller of the heat pump convectors User interface INFORMATION Mixing valve station Pressure regulating valve To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heat pump INFORMATION convector. A pressure regulating valve should be implemented before Configuration the mixing valve station.
▪ Make sure the auxiliary boiler and its integration in the ▪ Under floor heating has the best performance with Altherma LT. system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe Setting up an auxiliary heat source situations in the auxiliary boiler system.
Selecting the volume and desired temperature for the DHW tank Auto Automatic consists of: Boiler Boiler Determining the DHW consumption (equivalent hot water volume at 40°C). Determining the volume and desired temperature for the DHW tank. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
▪ When the heat pump produces domestic hot water, it cannot heat up a space. When you need domestic hot water and space heating at the same, Daikin recommends to produce the domestic hot water during the night when there is lower space heating demand.
▪ Maximum running current (in A) Use a three-phase power meter. ▪ Maximum power input (in kW) ▪ The power limitation level can be activated: ▪ Permanently ▪ By digital inputs Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
5.6.3 Power limitation process management system. The power or current of the entire Daikin system is limited The compressor has better efficiency than the electrical heater. dynamically by digital inputs. Power limitation level is set via the user Therefore, the electrical heater is limited and turned OFF first. The...
Plastic parts may deteriorate and fall for example, door opening/closing off or cause water leakage. ▪ If this is NOT possible, Daikin recommends to connect a remote ▪ Sound sensitive areas (e.g. near a bedroom and the like), so that indoor sensor (option KRCS01-1).
Page 19
Zn coated parts used in the brine circuit may The following illustration is an example and might NOT lead to the precipitation of certain components in the anti-freeze match your system layout. fluids corrosion inhibitor. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
▪ The corresponding maximum water volume at 0.3 bar is 350 l. (See the graph in the chapter above). ▪ Because 300 l is lower than 350 l, the expansion vessel is appropriate for the installation. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Whether the power supply is interrupted or not, the wiring to the unit is different. The following illustration shows the required field wiring. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
500 m. Applicable for both single user interface and dual use interface connection. NOTICE More technical specifications of the different connections are indicated on the inside of the indoor unit. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
You have to mount the indoor unit before you can connect the brine and water piping. Typical workflow Mounting the indoor unit typically consists of the following stages: Installing the indoor unit. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Check that the heat pump module does NOT touch the Also read the precautions and requirements in the outer casing. following chapters: ▪ General safety precautions ▪ Preparation EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
The piping in the complete brine circuit MUST be insulated to prevent reduction of the heating capacity. Consider that the brine circuit piping inside the house can/will condensate. Foresee adequate insulation for these pipes. Brine manometer Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
7.5.5 To connect the pressure relief valve to the drain The blow out of the pressure relief valve is coming out of the backside of the unit. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
11 Connecting the changeover to an external heat source. 12 Connecting the power consumption digital inputs. Water manometer 5 Purge as much air as possible from the water circuit. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
1× A´ 1× a Curled single core wire b Screw c Flat washer Stranded conductor wire with round crimp-style terminal a Terminal b Screw c Flat washer EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Do NOT push or place redundant cable length in the unit. 7.6.6 To connect the main power supply 1 Connect the main power supply. In case of normal kWh rate power supply Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Notch this part for the wiring to pass through with nippers etc. Secure the wiring to the front part of the casing using the wiring retainer and clamp. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Installation of EKRP1HB is required. 2 Plug the user interface cover into the hinges. 2 Fix the cable with cable ties to the cable tie mountings. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
To set the user permission level to Installer 1 Set the user permission level to Adv. end user. 2 Go to [6.4]: > Information > User permission level. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Are you sure you want to 6 Push to confirm the modification of the parameter. start the copy operation? 7 At installer settings menu, press to confirm the settings. Cancel Confirm Adjust EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Time What is the current time? : 00 Confirm Adjust Scroll 3 Set the system layout settings: Standard, Options, Capacities. For more details, see "8.2 Basic configuration" on page 36. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 37
▪ a: Space heating control (user interface) ▪ b: OFF ▪ c: On ▪ d: Pump operation continued >> ▪ a: Main LWT zone continued >> EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
The following parameters set the units freeze up prevention limit temperature. To allow temperature measurement tolerances, brine concentration MUST resist to a lower temperature than the defined setting. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 39
(X2M/1). Select this value in case of a [C-09] Alarm No alarm No power connection heat pump supply to unit convector (FWXV). 0 (default) Closed output Open output Open output Open output Closed output EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
The weather-dependent installer settings define the parameters for the weather-dependent operation of the unit. When weather-dependent operation is active, the water temperature is determined automatically depending on the Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 41
▪ fixed in time (i.e., NOT scheduled) ▪ Weather dep. (default): The desired leaving water temperature is: ▪ weather-dependent (i.e. depends outdoor ambient temperature) ▪ fixed in time (i.e., NOT scheduled) continued >> EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 42
Temperature difference Note: The desired leaving water Target leaving water temperature (main) temperature can only be read out on For leaving water temperature set point>60°C the user interface Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
▪ comfort (denotes the desired leaving water temperature which results in the highest energy consumption). EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 44
NOT to be able to heat up the room: leaving water ▪ 4 (enabled) L=4°C, temperatures must be sufficiently higher than the room temperatures R=8°C (−4°C<T <4°C) (in heating). Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 45
Only applicable in case of room thermostat control. The hysteresis ([2‑05]), the unit will supply leaving water to the heat emitters to heat band around the desired room temperature is settable. Daikin up the room again. recommends NOT to change the room temperature hysteresis as it is set for an optimal use of the system.
▪ reheat NOTICE ▪ reheat hysteresis For the (limited) frost protection to be possible, auto emergency MUST be set to Automatic ([A.5.1.2]=1). [C‑07]=0: leaving water temperature control Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 47
Range: 2°C~20°C (default: 2°C) [6-01] The temperature difference determining the heat pump OFF temperature. Range: 0°C~10°C (default: 2°C) Example: setpoint (T )>maximum heat pump temperature–[6‑01] –[6‑01]) HP MAX EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 48
Maximum running time domestic hot water Disinfection The disinfection function disinfects the domestic hot water tank by periodically heating the domestic hot water to a specific temperature. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Be sure that the disinfection function start time [A.4.4.3] allowed. with defined duration [A.4.4.5] is NOT interrupted by possible domestic hot water demand. Range: –15°C~35°C (default: 0°C) (step: 1°C) EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Make sure to observe all rules mentioned in application guideline 5 when bivalent operation function is enabled. Auto emergency Daikin shall NOT be held liable for any damage resulting When the heat pump fails to operate the backup heater can serve as from failure to observe this rule.
Page 51
The average timer corrects the influence of ambient temperature variations. The weather-dependent set point calculation is done on the average outdoor temperature. The outdoor temperature is averaged over the selected time period. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 52
This functionality is only valid in specific conditions where it is preferable to keep the pump active when <4°C (pump will be activated for 10 minutes and deactivated after 10 minutes). Daikin shall NOT be held liable for any damage resulting this functionality. Code...
▪ Outdoor unit relates to outdoor unit PCB which controls is valid. the compressor module of the ground source heat pump. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Settings shall NOT be used or changed. be visible/invisible. INFORMATION Power saving settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
There are no odour traces noticeable of the used brine. check if the circuit is sufficiently filled with water. Only if water escapes the valve after opening it, you can start the air purge procedure. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
2 Start the brine pump test run. 3 Start the brine filling station (MUST be started within a time frame of 5~60 seconds after starting the brine pump test run). Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
INFORMATION There is limited access to the menu structure. Only the following menus can be accessed: ▪ Information. ▪ Installer settings > Commissioning > UFH screed dryout. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Handle the space heating circuit filter with care. Do NOT persons. use excessive force when you reinsert the water filter so as NOT to damage the water filter mesh. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
DANGER: RISK OF ELECTROCUTION 2 The drain hose is located at the right side of the unit. Cut the tie wraps or tape and bring the flexible drain hose forward. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
(see "6.3.3 To check the water volume and flow rate of the space heating circuit and brine circuit" on page 20 "6.3.4 Changing the pre-pressure of the expansion vessel" on page 21). Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
For a more detailed troubleshooting guideline for each error, please Heat sources > Backup heater see the service manual. > Equilibrium temp. OR ▪ [A.8] > Installer settings > Overview settings [5‑01] EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
▪ Outdoor unit relates to outdoor unit PCB which controls the compressor module of the ground source heat pump. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Water filter brine circuit Water filter water circuit Water IN connection 22 mm straight Water OUT connection 22 mm straight Tank IN connection 22 mm straight Tank OUT connection 22 mm straight Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 67
Note 2: A flexible hose is pre-assembled to the drain outlet. The exit of the flexible hose is at the backside of the unit. The flexible hose can be removed. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Only for *KRUCBL* 2 core 2x0.75 A2P: P1-P2 user interface communication Note: - In case of signal cable: keep minimum distance to power cables > 5 cm 4D081378-1A Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Quantity Water volume 2.30 l Minimum water flow rate 8.0 l/min Nominal water Heating 29.2 l/min flow rate Heating 26.6 l/min Maximum water Heating 43.0 l/min flow rate Insulation material Green felt EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 80
Minimum water volume 20.0 l Water circuit domestic hot water side Piping connections Cold water in/hot water out Ø 22 mm Recirculation connection G 1/2" female Brine circuit Piping connections Ø 28 mm Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 81
Minimum 0.75 mm For connection with R6T Quantity of wires Type of wires Minimum 0.75 mm For connection with A3P Quantity of wires Note Type of wires Note and Note EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
(Tf) in the controller. The unit will NOT operate at an entering brine temperature lower than Tf+10K. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Page 83
(Tf) in the controller. The unit will NOT operate at an entering brine temperature lower than Tf+10K. Tf = changeable between 0°C and –15°C. EGSQH10S18AA9W Installer reference guide Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Mixture water/propylene glycol (40 V%) at entering brine temperature –5°C Mixture water/ethanol (29 M%) at entering brine temperature –5°C Note: Selecting a flow outside the area of operation can cause damage or malfunction of the unit. Installer reference guide EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1D – 2016.02...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment not made by Daikin that can be combined with product according instructions accompanying documentation.
ID4302/4562 Field settings table [6.8.2] = ..Applicable indoor units *GSQH10S18AA9W ThermaliaC12* Notes 4P359382-1D - 2015.02...
Page 87
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 21°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 19°C └─...
Page 88
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.3.1.1.1 LWT setpoint mode 0: Fixed 1: Weather dep. 2: Fixed / scheduled 3: WD / scheduled A.3.1.1.2.1 [9-01] Temperature range Minimum temp (heating) 15~37°C, step: 1°C...
Page 89
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value A.6.3.5.1 [5-05] Amp. limits for DI Limit DI1 0~50 A, step: 1 A 50 A A.6.3.5.2 [5-06] Amp. limits for DI Limit DI2 0~50 A, step: 1 A 50 A...
Page 90
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [3-00] Is auto restart of the unit allowed? 0: No 1: Yes [3-01] [3-02] [3-03] [3-04] [3-05] [3-06] What is the maximum desired room temperature in heating? 18~30°C, step: A.3.2.4 30°C [3-07]...
Page 91
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [8-08] [8-09] What is the desired comfort main LWT in heating? [9-01]~[9-00], step: 1°C 55°C [8-0A] What is the desired eco main LWT in heating? [9-01]~[9-00], step: 1°C 45°C [8-0B]...
Page 92
Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [D-09] Is an external kWh meter used for power measurement? 0 (No): NOT installed 1: Installed (0.1 pulse/kWh) 2: Installed (1 pulse/kWh) 3: Installed (10 pulse/kWh) 4: Installed (100 pulse/kWh) 5: Installed (1000 pulse/kWh)