Modbus Memory Map Notes - GE Multilin EPM 6000 Instruction Manual

Multi-function power meter
Hide thumbs Also See for Multilin EPM 6000:
Table of Contents

Advertisement

CHAPTER 5: COMMUNICATIONS
HEX
DESCRIPTION
ADDRESS
7550
- 7554
Limit #2
7555
- 7559
Limit #3
755A
- 755E
Limit #4
755F
- 7563
Limit #5
7564
- 7568
Limit #6
7569
- 756D Limit #7
756E
- 7572
Limit #8
SECONDARY READINGS SECTION
Secondary Block
9C40
- 9C40
System Sanity Indicator UINT16
9C41
- 9C41
Volts A-N
9C42
- 9C42
Volts B-N
9C43
- 9C43
Volts C-N
9C44
- 9C44
Amps A
9C45
- 9C45
Amps B
9C46
- 9C46
Amps C
9C47
- 9C47
Watts, 3-Ph total
9C48
- 9C48
VARs, 3-Ph total
9C49
- 9C49
VAs, 3-Ph total
9C4A - 9C4A Power Factor, 3-Ph total UINT16
9C4B - 9C4B Frequency
9C4C - 9C4C Volts A-B
9C4D - 9C4D Volts B-C
9C4E
- 9C4E
Volts C-A
9C4F
- 9C4F
CT numerator
9C50
- 9C50
CT multiplier
9C51
- 9C51
CT denominator
9C52
- 9C52
PT numerator
9C53
- 9C53
PT multiplier
9C54
- 9C54
PT denominator
9C55
- 9C56
W-hours, Positive
9C57
- 9C58
W-hours, Negative
9C59
- 9C5A VAR-hours, Positive
9C5B - 9C5C VAR-hours, Negative
9C5D - 9C5E
VA-hours
9C5F
- 9C5F
Neutral Current
9C60
- 9CA2 Reserved
Reset Energy
9CA3 - 9CA3
Accumulators
5.1.3

Modbus Memory Map Notes

EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
1
FORMAT
RANGE
SINT16
SINT16
SINT16
SINT16
same as Limit #1
SINT16
SINT16
SINT16
0 or 1
UINT16
2047 to 4095
UINT16
2047 to 4095
UINT16
2047 to 4095
UINT16
0 to 4095
UINT16
0 to 4095
UINT16
0 to 4095
UINT16
0 to 4095
UINT16
0 to 4095
UINT16
2047 to 4095
1047 to 3047
UINT16
0 to 2730
UINT16
2047 to 4095
UINT16
2047 to 4095
UINT16
2047 to 4095
UINT16
1 to 9999
UINT16
1, 10, 100
UINT16
1 or 5
UINT16
1 to 9999
UINT16
1, 10, 100
UINT16
1 to 9999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT16
0 to 4095
N/A
N/A
5
UINT16
password
The memory map notes are indicated by number below.
1.
All registers not explicitly listed in the table read as 0. Writes to these registers will be
accepted but won't actually change the register (since it doesn't exist).
UNITS OR
6
RESOLUTION
same as Limit #1
same as Limit #1
Block Size:
read-only except as noted
none
0 indicates proper meter operation
volts
2047= 0, 4095= +150
volts
volts = 150 * (register - 2047) / 2047
volts
amps
0= -10, 2047= 0, 4095= +10
amps
amps = 10 * (register - 2047) / 2047
amps
watts
0= -3000, 2047= 0, 4095= +3000
VARs
watts, VARs, VAs =
VAs
3000 * (register - 2047) / 2047
1047= -1, 2047= 0, 3047= +1
none
pf = (register - 2047) / 1000
0= 45 or less, 2047= 60, 2730= 65 or
Hz
more
freq = 45 + ((register / 4095) * 30)
volts
2047= 0, 4095= +300
volts
volts = 300 * (register - 2047) / 2047
volts
none
CT = numerator * multiplier /
none
denominator
none
none
PT = numerator * multiplier /
none
denominator
none
Wh per energy format * 5 to 8 digits
* decimal point implied, per energy
Wh per energy format
format
VARh per energy format * resolution of digit before decimal
point = units, kilo, or mega, per energy
VARh per energy format
format
VAh per energy format * see note 10
amps
see Amps A/B/C above
none
write-only register; always reads as 0
Block Size:
COMMENTS
# REG
5
5
5
5
5
5
5
68
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
1
67
1
100
5–7