Grounding - Mitsubishi Electric MELSEC iQ-F FX5U User Manual

Programmable controller
Hide thumbs Also See for MELSEC iQ-F FX5U:
Table of Contents

Advertisement

■Tool
For tightening terminals, use a small, commercially-available screwdriver with a straight tip. The recommended
shape is shown in the figure on the right.
■Precautions
When a precision screwdriver with a small grip is used, the specified tightening torque cannot be obtained. Use
the following screwdriver or equivalent product (grip diameter: 25 mm) to obtain the tightening torque specified
above.
<Reference>
Manufacturer
Phoenix Contact GmbH & Co. KG
6.3

Grounding

Perform the following.
• Perform class D grounding (Grounding resistance: 100  or less).
• Ground the PLC independently when possible.
• If the PLC cannot be grounded independently, perform the "Shared grounding" shown below.
Other
PLC
equipment
Independent grounding
(Best condition)
PLC extension devices (excluding expansion boards and communication adapters)
PLC
Expansion
Expansion
adapter
board
• Use a grounding wire with thickness of AWG 14 (2 mm
• Bring the grounding point close to the PLC as much as possible so that the ground cable can be shortened.
Model
SZS 0.42.5
Other
PLC
equipment
Shared grounding
(Good condition)
CPU
Extension
module
module
Independent grounding
class D grounding (grounding resistance: 100  or less)
2
) or thicker.
0.4 mm
Other
PLC
equipment
Common grounding
(Not allowed)
Other
Intelligent
equipment
module
With straight tip
2.5 mm
6
6 WIRING
95
6.3 Grounding