Mitsubishi Electric MELSEC iQ-F FX5U User Manual page 72

Programmable controller
Hide thumbs Also See for MELSEC iQ-F FX5U:
Table of Contents

Advertisement

■Number of remote I/O points
(Page 55 Calculation of number of remote I/O points)
Network
AnyWireASLINK
Remote I/O points
64 points
■Total number of I/O points and remote I/O points
(Page 53 Limitation on the Number of Input/Output Points)
Total number of input/output points
Number of input/output points
152 points
4 SYSTEM CONFIGURATION
70
4.5 Rules of System Configuration and Examples of Reconfiguration
No. of remote I/O points
64 points
Maximum number of
Remote I/O points
≤ 384 points
Remote I/O points
+
64 points
OK
Calculation result
= 216 points
Max. number of
input/output points
OK
512 points