Transistor output
For output specifications of the CPU module, refer to Page 25 Output Specifications.
For output specifications of the I/O modules, refer to Page 173 Output specifications.
For output specifications of the terminal modules, refer to Page 188 Output specifications.
Sink and source output
Sink output and source output products are available for transistor outputs of the CPU module, I/O modules, and terminal
modules.
■Differences in circuit
•
Sink output [-common]
Output to make load current flow into the output (Y) terminal is
called sink output.
Load
Y
COM
Fuse
DC power supply
A number is entered in the of [COM].
Handling of transistor output
■Output terminal
For the CPU module, output module (extension cable type), powered input/output module and high-speed pulse input/output
module, the transistor output type is a 4-point or 8-point common output type.
•
Sink output
Connect each COM (number) terminal to the minus side of
the load power supply.
The COM terminals are not connected internally.
Load
Y0
Y1
DC power
Fuse
supply
COM0
Load
Y4
Y5
DC power
Fuse
supply
COM1
For the output module (extension connector type) and input/output module, the transistor output type is an 8-point common
output type.
•
Sink output
The COM (number) terminals that are connected each other inside
the PLC are prepared. For external wiring, connect the COM
(number) terminals outside the PLC to reduce the load per one
COM terminal.
Load
Y0
Y1
Fuse
COM0
DC
COM0
power supply
•
Source output [+common]
Output to make load current flow out of the output (Y) terminal
is called source output.
Load
Y
+V
Fuse
DC power supply
A number is entered in the of [+V].
•
Source output
Connect +V (number) terminal to the plus side of the load
power supply.
The +V terminals are not connected internally.
Load
Y0
Y1
DC power
Fuse
supply
+V0
Load
Y4
Y5
DC power
Fuse
supply
+V1
• Source output
The +V (number) terminals that are connected each other inside the
PLC are prepared. For external wiring, connect the +V (number)
terminals outside the PLC to reduce the load per one +V terminal.
Load
DC power
supply
+V0
Fuse
+V0
Y0
Y1