■Transistor/sink output (FX-16EYT-TB, FX-16EYT-ES-TB/UL)
Item
Output type
External voltage
Max. load
Resistance load
Inductive load
Min. load
Open circuit leakage current
Response time
ON voltage of output element
Insulation of circuit
Indication of output operation
Power consumption
Input/output configuration
FX-16EYT-TB
circuit
FX-16EYT-ES-TB/UL
Unsupported applications
Specifications
Transistor/sink output
5 to 30 V DC
0.5 A/point
The total load current per common terminals (four points) should be 0.8 A or less.
12 W/24 V DC
0.1 mA/30 V DC
OFFON
0.2 ms or less/24 V DC
ONOFF
1.5 ms or less/24 V DC
1.5 V
Photo-coupler insulation
LED is lit when the power is supplied to photo-couplers.
2.7 W (112 mA 24 V DC)
Photo-
3.3
k
coupler
24+
CN1
24 V DC
connector
7 mA
LED
side
Photo-
3.3
k
coupler
24-
CN1
24 V DC
connector
LED
7 mA
side
Positioning, Pulse Y Output ((D)PLSY) instruction, Pulse Width Modulation ((D)PWM) instruction,
ABS Current Value Read (DABS) instruction, Start/stop of high-speed I/O function ((D)HIOEN)
instruction, Input Matrix (MTR) instruction, Digital Switch (DSW) instruction, Seven Segment With
Latch (SEGL) instruction
Fuse
0 to 7
5 to 30 V DC
COMn
External wiring
Fuse
0 to 7
5 to 30 V DC
COMn
External wiring