Check of limitation on the number of input/output points
Check if the number of input/output points of the sample system configuration is within the limit range.
■Number of input/output points
(Page 54 Calculation of number of input/output points)
Type
CPU module
Expansion board
Expansion adapter
Expansion adapter
Input module
Output module
Output module
Output module
Simple motion module
Bus conversion module
Pulse output module
Analog input module
Temperature controller module
AnyWireASLINK master module
CC-Link intelligent device module
Number of
input/output points
96 points
■Number of remote I/O points
(Page 55 Calculation of number of remote I/O points)
Network
AnyWireASLINK
Remote I/O points
64 points
■Total number of I/O points and remote I/O points
(Page 53 Limitation on the Number of Input/Output Points)
Total number of input/output points
Number of input/output points
152 points
4 SYSTEM CONFIGURATION
66
4.5 Rules of System Configuration and Examples of Reconfiguration
Model
FX5U-32MR/ES
FX5-232-BD
FX5-232ADP
FX5-485ADP
FX5-16EX/ES
FX5-16EYT/ES
FX5-16EYT/ES
FX5-16EYR/ES
FX5-40SSC-S
FX5-CNV-BUS
FX3U-1PG
FX3U-4AD
FX3U-4LC
FX3U-128ASL-M
FX3U-64CCL
Number of input/output points
Number of occupied
input/output points
+
56 points
No. of remote I/O points
64 points
Maximum number of
Remote I/O points
≤ 384 points
Remote I/O points
+
64 points
No. of input/output
points
32 points
16 points
16 points
16 points
16 points
Calculation result
=
152 points
OK
Calculation
result
= 216 points
No. of occupied input/
output points
8 points
8 points
8 points
8 points
8 points
8 points
8 points
Max. number of
input/output points
OK
256 points
Max. number of
input/output points
512 points
OK