■Triac output (FX-16EYS-TB, FX-16EYS-ES-TB/UL)
Item
Output type
External voltage
Max. load
Resistance load
Inductive load
Min. load
Open circuit leakage current
Response time
ON voltage of output element
Insulation of circuit
Indication of output operation
Power consumption
Input/output configuration
FX-16EYS-TB
circuit
FX-16EYS-ES-TB/UL
Unsupported applications
Specifications
Triac (SSR)
85 to 242 V AC
0.3 A/point
The total load current per common terminals (four points) should be 0.8 A or less.
15 VA/100 V AC
36 VA/200 V AC
0.4 VA/100 V AC
1.6 VA/200 V AC
1 mA/100 V AC
2 mA/200 V AC
2 ms or less
Photo-coupler insulation
LED is lit when the power is supplied to photo-thyristors.
2.7 W (112 mA 24 V DC)
3.3 k
24 V DC 7 mA
24+
CN1
connector
Photothyristor
LED
side
3.3 k
24 V DC 7 mA
24-
CN1
connector
Photothyristor
side
LED
Positioning, Pulse Y Output ((D)PLSY) instruction, Pulse Width Modulation ((D)PWM) instruction,
ABS Current Value Read (DABS) instruction, Start/stop of high-speed I/O function ((D)HIOEN)
instruction, Input Matrix (MTR) instruction, Digital Switch (DSW) instruction, Seven Segment With
Latch (SEGL) instruction
Fuse
0 to 7
36
0.015
F
COMn
External wiring
Fuse
0 to 7
36
0.015
F
COMn
External wiring