FX1N Series Programmable Controllers
DC Power supply, 12V DC, +20%/ -15%
Circuit protector or Fuse
Emergency stop
Power supply switch
Power ON pilot indicator
Power supply for loads
Grounding resistor 100Ω or less
4.6

Service Power supply

An AC powered FX
and, when used with extension or special function blocks.
A DC powered FX
Additional extension blocks can be powered from the main units power supply.
4.7

Earthing / Grounding

Use a cable at least 0.2mm
less than 100Ω. Note that the ground cable must not be connected to the same ground as
the power circuits.
can supply a service current of 24V DC at 400mA when used on its own
1N
does not have the capacity to supply a service current. However
1N
2
(AWG24) to ground equipment. Ground resistance must be
Fuse
Main unit
Breaker
Power Supply for the input circuitry of the
main unit and extension blocks that are
11
connected.
When using a 12V DC power supply,
extension blocks occupying up to 32
12
I/O points are connected.
Power Supply 4.
1
2
3
4
5
6
7
8
4-9