The "One Man" Test mode gives the installer the possibility to test the efficiency of the
system - whether the detectors react to smoke, heat, etc.
Z
To "One Man" Test a zone:
• Press
TEST/ SCROLL:
• Press
TEST/ SCROLL
again:
• Press
TEST/ SCROLL
again to continue with the sys-
tem testing:
Continue the system testing by pressing the "
the "One Man" Test mode is automatic after the end of the test procedure in the last Zone
8, or at any time by pressing "
Quick Reference Operation Examples
• To disable Zone 3, do in sequence:
To enable back the Zone 3 do the same steps. At the end the Zone 3 and ENABLE /
DISABLE LED are off.
• To disable the sounders, do in sequence:
To enable back the sounders do the same steps. At the end the SOUNDER FAULT/
DISABLE and ENABLE / DISABLE LED are off.
- The LED is off;
LEGEND:
Fire Control Panel MAG8 - Installation and Operation Manual
TEST LED will start blinking.
µP Fault LED lights off. All other system indication
LEDs light on permanently.
The ZONE 1 yellow LED starts blinking.
ZONE 1 is in test mode. Test a detector from this
zone whether it react to smoke, heat, etc.
TEST LED will continue blinking.
The ZONE 1 yellow LED lights out (the zone is
not longer in test mode). The ZONE 2 yellow LED
blinks in yellow.
ZONE 2 is in test mode. Test a detector from this
zone whether it react to smoke, heat, etc.
RESET" button.
x 8 times
- The LED is on;
TEST/ SCROLL" button. The exit from
At the end the yellow Zone 3 LED and
ENABLE / DISABLE LED light on
At the end the SOUNDER FAULT/
DISABLE LED and ENABLE / DIS-
- The LED blinks
ABLE LED light on
15