CLEARANCES WITH VIGNETTE FACEPLATE

Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
The clearances listed below are Minimum
distances unless otherwise stated:
A major cause of chimney related fires is
failure to maintain
required clearances (air space) to combus-
tible materials.
It is of the greatest importance that this
fireplace and vent system
be installed only in accordance with these
instructions.
Clearance to Combustibles from:
Back
0"
Side
0"
Floor
0"
NOTE: The minimum floor clearance must
be maintained from the top surface of the
carpeting, tile, etc.

MANTEL LEG CLEARANCES WITH VIGNETTE FACEPLATE

Combustible mantel leg clearances from side of unit as per diagram:
Minimum Clearance from Top of Unit to:
Mantel*
Ceiling
from top of unit.
Side Wall Clearance
Minimum Vent Clearances:
2-1/2" (64mm) Horizontal Top
1-1/2" (38mm) Horizontal Side
1-1/2" (38mm) Horizontal Bottom
1-1/4" (32mm) Vertical Vent Clearance
(Rigid Vent)
1-1/2" (38mm) Vertical Vent Clearance
(0mm)
(Flex Vent)
(0mm)
(0mm)
Alcove Clearances:
Max. Depth
Min. Width
Min. Height
* see mantel clearance instructions.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
min. 10"(254mm)
30"
(762mm)
7-1/2" (191mm)
36"
(914mm)
48"
(1219mm)
Fire hazard is an extreme risk if these
59"
(1499mm)
clearances are not adhered to.
Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace
installation
Clearances for Vignette Faceplate
Warning
|
11
|
11