Regency PANORAMA P33E Owners & Installation Manual page 24

Hide thumbs Also See for PANORAMA P33E:
Table of Contents

Advertisement

installation
|
24
The P33E-10 is approved for a maximum 40 ft. straight vertical, with rigid
pipe vent systems for Propane and Natural Gas.
The shaded area in the diagram shows all allowable combinations of straight
vertical and offset to vertical terminations with rigid pipe vent systems for
Propane and Natural Gas. Maximum two 45
Vent must be supported at offsets.
Firestops are required at each floor level and whenever passing
through a wall.
Maintain clearances to combustibles.
24 |
Regency® P33E-10 Zero Clearance Direct Vent Gas Fireplace
elbows allowed.