Setting The User Parameters - Beretta POWER PLUS Installation Instruction

Wall-hung condensing boiler
Hide thumbs Also See for POWER PLUS:
Table of Contents

Advertisement

Value displayed
8
Operating status of the mixing valve
E.g.: closing, opening, standby
9
Operating status of the main pump
E.g.: pump not working, pump working
10
Operating status of the DHW pump
E.g.: pump not working, pump working
11
Operating status of the secondary pump
E.g.: pump not working, pump working
To exit the display of the values, press the "OK" button.
If no operation is performed for 5 minutes, the board automatically returns to Readout mode.

SETTING THE USER PARAMETERS

Pressing "[" displays the following values in sequence:
- Outlet temperature T1 in the high temperature circuit
- DHW temperature T3
- Outlet temperature in the second circuit or low temperature circuit T6.
To change the corresponding set points:
- Press "Set/esc", the corresponding value will be displayed and the two digits on the right will flash.
- If the value needs to be changed, press "
The value displayed will stop flashing and the display will return to Readout mode.
Example: changing the set point in the low temperature circuit from 50°C to 40°C
Procedure
1
E.g.: Value read on the display in the high temperature circuit 80°C
2
Press "[" to access Readout mode, press the button again
and scroll the first digit to 6 so as to display the set value, E.g.: 50°C
+
-
" or "
" until reaching the desired value. Press "OK" to save the new value.
Display
Display
21