Adjustments
The POWER PLUS Boiler is supplied for operation on
G20 (natural gas), as indicated on the rating plate, and
has already been adjusted in the factory by the manu-
facturer.
If, however, the adjustments need to be performed again,
for example after special servicing operations, the repla-
cement of the gas valve, or alternatively following the
conversion from G20 to G30-G31 or vice-versa, proceed
as follows.
CO
ADJUSTMENT AT MAXIMUM OUTPUT
2
- Press the "Set/esc" and "+" buttons together for 5s.
- Start the boiler by adjusting the room thermostat.
The boiler will operate at maximum output showing
"H" on the display, followed by the outlet temperature
(chimney sweep function).
- Unscrew the cap (1) and insert the combustion analy-
ser probe
- Adjust the CO
screw (2) located on the fan assembly (turning
clockwise decreases the CO
ve a value of 9.0% for G20 and 10.4% for G30-G31.
CO
ADJUSTMENT AT MINIMUM OUTPUT
2
- Press the "Set/esc" and "-" buttons together for 5s.
The boiler will operate at minimum output showing "L"
62
on the display, followed by the outlet temperature.
- Adjust the CO
screw (3) located on the fan assembly (turning anti-
clockwise decreases the CO
ve a value of 9.0% for G20 and 10.4% for G30-G31.
CHECKING THE CALIBRATION
Press the "Set/esc" and "+" buttons together for 5s and
check the max CO
G30-G31). Then press the "Set/esc" and "-" buttons
for 5s and check the min CO
10.4% for G30-G31).
After having completed the checks:
- Stop the chimney sweep function by pressing "OK"
- Adjust the thermostat so as to stop the boiler
- Remove the analyser probe and carefully retighten the
cap (1).
using a screwdriver on the adjustment
2
value), so as to achie-
2
using a screwdriver on the adjustment
2
value), so as to achie-
2
value (9.0% for G20 and 10.4% for
2
value (9.0% for G20 and
2
b
The adjustments at maximum and minimum
output must be carried out in the sequence
described, and only by BERETTA or personnel
authorised by BERETTA.
b
After adjusting the gas valve, seal it with sealing
wax.