Beretta POWER PLUS Installation Instruction page 59

Wall-hung condensing boiler
Hide thumbs Also See for POWER PLUS:
Table of Contents

Advertisement

No. Name
lower
limit
26 CH_low_hyst_on
27 CH_low_hyst_off
28 Mix_valve_step_ open_time 0
29 Mix_valve_step_close_time 0
30 Mix_valve_interval_time 0
31 Mixing_p_hyst
32 Mixing_still_hyst
33 Power control mode
34 3
rd
pump
35 Frost protection
-30
36 Gas_type
37 T_out_min
-20
38 T_out_max
39 T_out_correct
-30
40 T_emergency
41 Parameter_reset
42 Flow switch on slave
43 Protocol
upper
default
limit
settinglimit
5
0
20
3
0
20
5
255
7
255
5
255
2
0
255
0
255
2
1
0
1
0
0
1
3
15
01
1
31
0
30
18
0
30
0
30
10
80
70
0
0
1
1
0
1
1
0
1
UOM
Description
limit
setting
°C
Start hysteresis in low circuit calculated
on the mixer outlet temp
°C
Stop hysteresis in low circuit calculated
on the mixer outlet temp
s
For each step the valve opens
1/2 of the set value
s
For each step the valve closes
1/2 of the set value
s
Mixing valve delay
°C
Hysteresis for maximum valve opening
°C
0 = Minimum number of burners
1 = Maximum number of burners
0 = System/loop
1 = Low temperature circuit
°C
System
01 = NG with flue < 15m
02 = NG with flue > 15m
03 = LPG with flue < 15m
04 = LPG with flue > 15m
°C
°C
°C
°C
0 = The slave does not control the pressure switch
0 = Eco protocol
1 = Argus link (new)
59