Setting The Addresses For Cascading Configurations - Beretta POWER PLUS Installation Instruction

Wall-hung condensing boiler
Hide thumbs Also See for POWER PLUS:
Table of Contents

Advertisement

Setting the Addresses for Cascading Configurations

The microswitches on the slave boards are factory-set so as to interface a master boiler (50 M, 100 M or 100 M DEP)
to a slave boiler (100 S or 100 S DEP). If further slave boilers need to be connected, only the microswitches on these
boilers will need to be reset.
Accessing the SLAVE boards
- Move the main system switch to "off"
- Access the slave boards inside the boiler control panel (see the steps described on page 65)
- Follow the address setting procedure described below, and then connect the boilers using the special bus cable (see
the wiring diagrams starting from page 14).
Setting the ADDRESSES
Each slave board (one for each heat generator) must be configured so as to be recognised in the right sequence by
the master board.
The slave generators should first of all be divided into blocks; the system can manage up to 15 blocks of four slave
generators each.
For example, if 5 slave generators are connected to a master, there are two blocks: the first made up of four slave gene-
rators and the second of one slave generator.
Consequently, the addresses should be set as follows:
- Identify the block of four that the slave generator being configured belongs to (for example block 1, 2, ........., up to
block15)
- Identify the position of the slave generator inside each block (e.g. position 1, 2, 3 or 4).
SLAVE address
54
BLOCK address
Table of SLAVE addresses
Microswitches
SLAVE
address
1
2
OFF
OFF
1
OFF
ON
2
ON
OFF
3
ON
ON
4
T3
J10
SLAVE board
J17
Table of BLOCK addresses
Microswitches
1
2
3
4
OFF OFF OFF OFF
Emergency
OFF OFF OFF ON
1st block
OFF OFF ON OFF
2nd block
OFF OFF ON
ON
3rd block
OFF ON OFF OFF
4th block
OFF ON OFF ON
5th block
OFF ON ON OFF
6th block
OFF ON ON
ON
7th block
ON OFF OFF OFF
8th block
ON OFF OFF ON
9th block
ON OFF ON OFF
10th block
OFF OFF ON
ON
11th block
ON ON OFF OFF
12th block
ON ON OFF ON
13th block
ON ON ON OFF
14th block
ON ON ON
ON
15th block
Main
BLOCK