Beretta Power Plus Box SE Installation Manual

Condensing / thermal modules

Advertisement

Quick Links

Installation Manual
Power Plus Box
CONDENSING | THERMAL MODULES
EN
Installation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Beretta Power Plus Box SE

  • Page 1 Installation Manual Power Plus Box CONDENSING | THERMAL MODULES Installation Manual...
  • Page 2 Plus Box SE Please accept our renewed thanks for your purchase Beretta CONFORMITY The Power Plus Box SE modular condensing systems com- ply with: - Directive 2009/142/EC - Gas Appliances - Directive 92/42/EEC on efficiency requirements and Annex E and Pres. Republic Decree n. 412, 26 Au-...
  • Page 3: Table Of Contents

    CONTENTS GENERAL INFORMATION General Safety Information ....4 Precautions ......4 Description of the appliance .
  • Page 4: General Information

    GENERAL INFORMATION 1 2 Precautions The operation of any appliance that uses fuel, electrical power and water demands that a number of fundamental 1 1 General Safety Information safety precautions be respected: Do not allow children or infirm persons to operate the After removing the packaging, check the condition system unsupervised.
  • Page 5: Description Of The Appliance

    1 3 Description of the appliance 1 4 Safety devices The Power Plus Box SE system is a module to be combined The Power Plus Box SE modular system is equipped with with a Power Plus Box system (SLAVE) for implementing a...
  • Page 6: Identification

    1 5 Identification The products are identified by: Paese di destinazione: Tipo di apparecchio Caldaia categoria 2H3+ Temperatura ambiente: min. -10°C max. 50°C Pressioni di alimentazione gas: G20 20 mbar G30 28-30 mbar G31 37 mbar Regolazione effettuata dal costruttore: G20 - 20 mbar - 2H METANO ATTENZIONE Questo apparecchio puó...
  • Page 8: Coupling Configuration

    1 7 Coupling configuration POWER PLUS BOX POWER PLUS BOX SE Delivery manifold sensor Low system temperature sensor Boiler sensor Outdoor sensor Zone 1 circulator (high temperature) Zone 2 circulator (low temperature) Boiler circulator Mixer valve...
  • Page 9: Technical Specifications

    1 8 Technical specifications MODEL Power Plus Box 100 SE Fuel G20 - G30 - G31 Device category II2H3+ Device type B23, B53 Furnace heat output ref. PCS (min - max) 16 - 100 Furnace heat output ref. PCI (min - max) 14,4 - 89,9 Useful heat output (80°/60°C) 88,3...
  • Page 10: Water Circuit

    1 9 Water circuit Low temperature return fitting Automatic bleed valve High temperature return fitting Burner Fuel shut-off cock Heat exchanger Maximum pressure switch Differential water and minimum pressure switch Fuel shut-off cock probe Non-return valve Heating delivery probe Pump Heating element delivery probe 3-way cock Safety thermostat (triggering at 90°C)
  • Page 11: Location Of Sensors

    80°C 60°C 50°C 30°C POWER PLUS BOX POWER PLUS BOX SE Install sensors SZ2 and SB in a trap (outside the modular system). Correspondence table for all sensors Measured temperatures (°C) - Resistive values of the sensors (Ω). T (°C) T (°C)
  • Page 12: Wiring Diagrams

    1 11 Wiring diagrams Ground star pole Ground star pole Connection by the installer Terra 230V~50Hz Neutro Fase J10 6 J11 7 Pump J10 5 J11 14 J10 4 J11 6 Pump J10 3 J11 13 J10 2 J11 5 Pump 3 J10 1 J11 12...
  • Page 13 al polo stella di terra al polo stella di terra EA/ER EA/ER Terra Terra Terra Terra Terra Terra Fusibile 4A Fusibile 4A Fase Fase Neutro Neutro Circolatore Circolatore Valvola gas Valvola gas Termostato limite Termostato limite Pressostato Diff. Pressostato Diff. SLAVE 1 SLAVE 2 Soffiante (+)
  • Page 14: Installation

    Remove the straps (1) and the cardboard packaging (2). 2 1 Unpacking the product 1 Strap 2 Cardboard packaging The Power Plus Box SE condensing system is supplied on 3 Pallet a pallet, strapped and protected by cardboard packaging. 4 Modular condensing system...
  • Page 15: Overall Dimensions And Weights

    2 3 Overall dimensions and weights 1250 IGAS CGAS CGAS 196,5 IGAS DESCRIPTION Power Plus Box 100 SE System side connections High temperature flow manifold 3" Ø Low temperature flow manifold 3" Ø High temperature return manifold 3" Ø Low temperature return manifold 3"...
  • Page 16: Installation Premises

    2 4 Installation premises The Power Plus Box SE system must be located next to a Power Plus Box system, as shown in the figure, and connected to it hydraulically by means of the 5” flanged manifolds. Also the gas manifold, flue gas manifold and the condensate outlet must be connected together.
  • Page 17: Water Connections

    2 5 Water connections The Power Plus Box SE condensing systems are designed and built to be installed in hot water heating systems and are always combined with a Power Plus Box system. They are used only for this purpose and any other erroneous or unreasonable application is prohibited.
  • Page 18: Water In Central Heating Systems

    WATER IN CENTRAL HEATING General note on water used to top up systems: - If softened water is used to top up a system, 8 weeks SYSTEMS of functioning after topping up, verify that the water in the system respects the above limits, in particular for INTRODUCTION electrical conductivity - This check is not necessary if demineralised water is...
  • Page 19 3.2 Stray current corrosion Corrosion from stray currents can occur due to the differ- ing electrical potentials between water in the boiler and the metallic mass of the boiler or piping. This process leaves unmistakeable traces i.e. small regular conical holes. All metallic parts should be grounded by an efficient earth cable for this reason.
  • Page 24 Commercial Offices: Via Risorgimento, 23 A 23900 - Lecco www.berettaboilers.com Beretta reserves the right to modify the characteristics and specifications given in this publication at any time and without prior notice as part of its policy of continuous product improvement.