List Of Parameters - Beretta POWER PLUS Installation Instruction

Wall-hung condensing boiler
Hide thumbs Also See for POWER PLUS:
Table of Contents

Advertisement

List of Parameters

No. Name
USER parameters
1
SetPoint_ch_high
2
SetPoint_DHW
3
SetPoint_ch_low
INSTALLER parameters accessible by password: 22
6
DHW_type
7
P_DHW_max
8
T_DHW_limit
9
DHW_priority
10 T_tank_extra
58
11 T_tank_hyst_up
12 T_tank_hyst_down
13 N°_burn_DHW
14 CH_type_high
15 P_ch_max
16 CH_priority
17 T_CH_high_limit
18 T_CH_high_foot
19 CH_high_hyst_on
20 CH_high_hyst_off
21 Attenuation_high
22 CH_type_low
23 T_CH_low_limit
24 T_CH_low_foot
25 Attenuation_low
(*) = 170 for 100 M DEP and 100 S DEP.
lower
upper
default
limit
limit
setting
10
Par. 17
10
Par. 8
10
Par. 23
0
6
230 (*)
1
255
10
80
0
2
0
50
0
20
0
20
1
60
0
3
230 (*)
1
255
0
2
10
80
10
Par. 1
0
20
0
20
0
70
0
3
10
70
10
Par. 13
0
70
UOM
Description
70
°C
If Par14=0 this is the high temperature circuit set
point. If Par14=1 this is the maximum temperature
in the high temperature circuit
50
°C
DHW set-point
40
°C
If Par22=0 this is the low temperature circuit set point
If Par22=1 this is the maximum temperature
in the low temperature circuit
0
0 = No DHW service
1 = Instant with NTC probe
2 = Storage heater with NTC probe
5 = Instant with flow switch
6 = Storage heater with thermostat
Maximum speed/output in DHW
60
Limit for user DHW setting
0
0 = Sliding A
1 = Sliding B
2 = Absolute priority
30
°C
Modular temp system in DHW = Par. 2 + Par. 10
1
°C
Upper DHW differential
5
°C
Lower DHW differential
60
Maximum no. of burners in DHW
1
0 = Fixed temperature
1 = Climate with outside probe
2 = 0-10 Vdc for heat output
3 = 0-10 Vdc for temperature
Maximum speed/output in CH
0
0 = No priority between circuits
1 = Priority to the high temperature circuit
2 = Priority to the low temperature circuit
80
°C
Limit for user high temperature circuit setting
50
°C
Min. high circuit set point at the maximum
outside temperature (Par. 38)
7
°C
Start hysteresis in high temperature circ.
3
°C
Stop hysteresis in high temperature circ.
0
°C
Set point attenuation with room thermo. open
1
0 = Fixed temperature
1 = Climate with outside probe
2 = 0-10 Vdc for heat output
3 = 0-10 Vdc for temperature
50
°C
Limit for user low temperature circuit setting
25
°C
Min. low circuit set point - at the maximum
outside temperature (Par. 38)
0
°C
Set point attenuation with room thermo. open