Frequency Setting By External Terminals; Operation By Multi-Speed Operation (Pr. 4 To Pr. 6, Pr. 24 To Pr. 27, Pr. 232 To Pr. 239) - Mitsubishi Electric FR-D720-008 Instruction Manual

Hide thumbs Also See for FR-D720-008:
Table of Contents

Advertisement

4.6

Frequency setting by external terminals

Purpose
Make frequency setting by
combination of terminals
Perform Jog operation
Infinitely variable speed setting by
terminals
4.6.1

Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)

Can be used to change the preset speed in the parameter with the contact signals.
Any speed can be selected by merely turning ON-OFF the contact signals (RH, RM, RL, REX signals).
Parameter
Name
Number
Multi-speed setting (high
4
speed)
Multi-speed setting (middle
5
speed)
Multi-speed setting (low
6
speed)
24 ∗
Multi-speed setting (speed 4)
25 ∗
Multi-speed setting (speed 5)
26 ∗
Multi-speed setting (speed 6)
27 ∗
Multi-speed setting (speed 7)
232 ∗
Multi-speed setting (speed 8)
233 ∗
Multi-speed setting (speed 9)
234 ∗
Multi-speed setting (speed 10)
235 ∗
Multi-speed setting (speed 11)
236 ∗
Multi-speed setting (speed 12)
237 ∗
Multi-speed setting (speed 13)
238 ∗
Multi-speed setting (speed 14)
239 ∗
Multi-speed setting (speed 15)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
* The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 160)
Speed 1
(High speed)
Speed 2
(Middle speed)
ON
RH
ON
RM
RL
REMARKS
In the initial setting, if two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency of
the lower signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
The RH, RM, RL signals are assigned to the terminal RH, RM, RL in the initial setting. By setting "0 (RL)", "1 (RM)", "2 (RH)" in
any of Pr. 178 to Pr. 182 (input terminal function selection), you can assign the signals to other terminals.
Multi-speed operation
Jog operation
Remote setting function
Initial Value
60Hz
30Hz
10Hz
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
(1)
Speed 3
(Low speed)
Time
ON

Frequency setting by external terminals

Parameter that should be Set
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 15, Pr. 16
Pr. 59
Setting Range
0 to 400Hz
0 to 400Hz
0 to 400Hz
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
3-Speed setting (Pr. 4 to Pr. 6)
The inverter operates at frequencies set in Pr. 4 when RH signal
is ON, Pr. 5 when RM signal is ON and Pr. 6 when RL signal is
ON.
Refer to Page
87
89
91
Description
Frequency when RH turns ON
Frequency when RM turns ON
Frequency when RL turns ON
Frequency from 4 speed to 15 speed can
be set according to the combination of
the RH, RM, RL and REX signals.
9999: not selected
4
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740-012Fr-d710w-008Fr-d720s-008

Table of Contents