Mitsubishi Electric FR-D720-008 Instruction Manual page 227

Hide thumbs Also See for FR-D720-008:
Table of Contents

Advertisement

(9)
Adjustment procedure
Dancer roller position detection signal adjustment
When terminal 4 input is voltage input, 0V is the minimum position and 5V(10V) is the maximum position. When current is
input, 4mA is the minimum position and 20mA is the maximum position. (initial value) When 0 to 7V is output from the
potentiometer, it is necessary to calibrate C7 (Pr .905) at 7V.
20mA
4mA
(Example) Control at a dancer center position using a 0 to 7V potentiometer
1) After changing the current/voltage input switch to "V", set "2" in Pr. 267 to change terminal 4 input to voltage input.
2) Input 0V to across terminal 4 and 5 to calibrate C6 (Pr. 904). (% display displayed at analog calibration is independent
to % of the feed back value.)
3) By inputting 7V to across terminal 4 to 5, calibrate C7(Pr. 905) (% display displayed at analog calibration is
independent to % of the feed back value.)
4) Set 50% in Pr.133.
NOTE
When the Pr. 267 setting was changed, check the voltage/current input switch setting. Different setting may cause a
fault, failure or malfunction. (Refer to page 148 for setting)
REMARKS
In normal PID control, PID control is stopped when multi-speed operation signal (RH, RM, RL, REX signal) or JOG signal is
input. In dancer control, however, PID control continues handling the signals as the main speed.
During dancer control, Second acceleration/deceleration time of Pr.44 and Pr.45 are the parameters for acceleration/deceleration
time setting to the main speed command source. These do not function as the second function.
When switchover mode is set with "6" in Pr. 79, dancer control (PID control) is invalid.
Speed command of terminal 4 input from terminal AU is invalid when dancer control is selected.
Acceleration/deceleration of the main speed command is the same operation as when frequency command is increased/
decreased by analog input.
Therefore, SU signal remains ON even if the starting signal is turned ON/OFF.(always in the constant speed state)
The DC brake operation starting frequency when turning OFF the starting signal is not Pr. 10 but a smaller value of either Pr. 13
or 0.5Hz.
The set frequency monitor is always variable as "main speed command+PID control".
The main speed setting frequency accelerates for the acceleration/deceleration time set in Pr. 44 and Pr. 45 and the output
frequency accelerates/decelerates for the acceleration/deceleration time set in Pr. 7 and Pr. 8. Therefore, when the set time of
Pr. 7 and Pr. 8 is longer than Pr. 44 and Pr. 45, the output frequency accelerates/decelerates for the acceleration/deceleration
time set in Pr. 7 and Pr. 8.
For the integral term limit, a smaller value of either the PID manipulated variable (%) value converted from the linear
interpolated Pr. 1 Maximum frequency with Pr. 902 and Pr. 903 , or 100% is used for limit.
Although the output frequency is limited by the minimum frequency, operation limit of the integral term is not performed.
Parameters referred to
Pr. 59 Remote function selection
Pr. 73 Analog input selection
Pr. 79 Operation mode selection
Pr. 178 to Pr. 182 (input terminal function selection)
Pr. 190, Pr. 192 (output terminal function selection)
Pr. 561 PTC thermistor protection level
C2 (Pr. 902) to C7 (Pr. 905) Frequency setting voltage (current) bias/gain
5V(10V)
0V
0%
100%
Feedback value
Refer to page 91
Refer to page 148
Refer to page 163
Refer to page 111
Refer to page 117
Refer to page 98
Special operation and frequency control
Upper limit
position
Lower limit
position
Refer to page 151
Potentiometer, etc.
223
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740-012Fr-d710w-008Fr-d720s-008

Table of Contents