Mitsubishi Electric FR-D720-008 Instruction Manual page 106

Hide thumbs Also See for FR-D720-008:
Table of Contents

Advertisement

Selection and protection of a motor
(2)
Use two motors (Pr. 450)
Set Pr. 450 Second applied motor to use two different motors with one inverter.
When "9999" (initial value) is set, no function is selected.
When a value other than 9999 is set in Pr. 450, the second motor is valid with the RT signal ON.
For the RT signal, set "3" in any of Pr. 178 to Pr. 182 (input terminal function selection) to assign the function.
REMARKS
The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 114)
NOTE
Changing the terminal assignment using Pr. 178 to Pr. 182 (input terminal function selection) may affect other functions.
Make setting after confirming the function of each terminal.
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Set the electronic thermal relay function to the thermal characteristic for the constant-torque motor when
using a geared motor (GM-G, GM-D, GM-SY, GM-HY2 series) to perform General-purpose magnetic flux vector
control.
Parameters referred to
Pr. 0 Torque boost
Pr. 12 DC injection brake operation voltage
Pr. 80 Motor capacity
102
CAUTION
Refer to page 71
Refer to page 107
Refer to page 103

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740-012Fr-d710w-008Fr-d720s-008

Table of Contents